3 Warranty, guarantee, liability
Operation manual
maximus L
13
maxi
mus
L
150
200
250
300
Emissions according to test
report:
Wood chips
Flue gas values (in relation to 13% O
2
)
from test report:testing institute/test
report No.
18-IN-AT-UW-OÖ-
EX-205/3
TÜV Austria
Interpolation accor-
ding to EN 303-5
18-IN-AT-UW-OÖ-
EX-205/4
TÜV Austria
-
CO full load
[mg/m³]
19
30
38
-
CO partial load
[mg/m³]
20
20
20
-
NO
X
full load
[mg/m³]
120
120
115
-
NO
X
partial load
[mg/m³]
93
93
93
-
Org. C full load
[mg/m³]
2
2
2
-
Org. C partial load
[mg/m³]
2
2
2
-
Dust content full load
[mg/m³]
9.5
11.6
6
-
Dust content partial load
[mg/m³]
6
6.5
6
-
Flue gas mass flow full load
[g/s]
97.9
130.5
156.7
-
Flue gas mass flow partial load
[g/s]
29.4
39.2
47.0
-
Emissions according to test
report:
Pellets
Flue gas values (in relation to 13% O
2
)
from test report:testing institute/test
report No.
18-IN-AT-UW-OÖ-
EX-205/1
TÜV Austria
Interpolation accor-
ding to EN 303-5
Interpolation accor-
ding to EN 303-5
18-IN-AT-UW-OÖ-
EX-205/2
TÜV Austria
CO full load
[mg/m³]
<3
3
3.6
3.6
CO partial load
[mg/m³]
29
29
29
29
NO
X
full load
[mg/m³]
112
112
113
113
NO
X
partial load
[mg/m³]
83
83
83
83
Org. C full load
[mg/m³]
2
2
2
2
Org. C partial load
[mg/m³]
2
2
2
5
Dust content full load
[mg/m³]
1
8
2
10.2
Dust content partial load
[mg/m³]
5
5
5
5
Flue gas mass flow full load
[g/s]
94.5
126.0
157.6
189.1
Flue gas mass flow partial load
[g/s]
28.4
37.8
47.3
56.7
[1]
Adjustable feet at maximum depth of thread
[2]
The boiler cladding parts are removed. The dimension including fitted cladding is 106 cm.
[3]
The minimum room height is required for maintenance work
[4]
A draught stabiliser must be fitted if the specified draught of 15 Pa is exceeded
[5]
Flue gas temperature can be adjusted electronically