40
L30US-IB80, L30US-IB00, L40US UPS
4.3.6.7.
Bypass settings
Bypass Volt Prot. Lower Limit:
When the difference between the bypass voltage and the
rated voltage exceeds the lower threshold for the bypass voltage, the system determines that
the bypass voltage is abnormal and that the bypass is unavailable. The value can be –10%, –
15%, –20%, –30%, –40%, The default value is –30%.
Bypass Volt Prot. Limit:
When the difference between the bypass voltage and the rated
voltage exceeds the upper threshold for the bypass voltage, the system determines that the
bypass voltage is abnormal and that the bypass is unavailable.
NOTE!
When the voltage level is 120V, the value range is 10%, 15%, 20%, 25%,
and 20% (default).
When the voltage level is 127 V, the value range is 10%, 15%, and 20%
(default).
Bypass Freq Tracking Range: When the difference between the bypass input frequency and
the rated frequency exceeds this value, the system determines that the bypass frequency is
not normal, and that the bypass is unavailable. The value range is
±
1%,
±
2%,
±
4%,
±
5%,
±
10%(default).
Bypass Rate Tracking Rate:
Inverter frequency tracking to bypass frequency rate. The value
range is 0.5~2Hz/s and is 1 by default.
Содержание L30US-IB00
Страница 2: ......
Страница 18: ...10 L30US IB80 L30US IB00 L40US UPS 3 5 Dimensions and Weight Figure 4 Dimensions...
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 51: ......
Страница 52: ......
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 58: ......
Страница 60: ......
Страница 61: ......
Страница 62: ......
Страница 78: ...4256 7784 C...