24
L30US-IB80, L30US-IB00, L40US UPS
Figure 19 Muser5000 UPS ID setting page
CAUTION!
After changing the parallel system ID, the connection between Muser5000 and
the equipment might be interrupted. If it happens, reconnect in accordance
with the instructions above.
CAUTION!
Parallel cable cannot be connected when setting the parallel parameters.
After setting the UPS systems that need to be paralleled, power off all the UPS systems.
Connect all the UPS systems in parallel cable installation, then power on the UPS systems.