6.Maintenance and repair

Check the water supply and air vent frequently, to avoid lack of water or air in the water 
loop. Clean the water filter 

 Lack of water and 

dirty  water can damage the unit. The heat pump will start the water pump per 

 

when it is not running, to avoid freezing. 

periodically, helping the water to stay clean.

every 72 hrs 

Keep the unit in a place which is dry and clean, and has good ventilation. Clean the heat 
exchanger 

every 1 to 2 months to keep a good heat exchange rate.

Check each part of the unit and the pressure of the system. 

 and recharge the 

refrigerant if it is needed.

Delete

If the heat pump is not used for a long time, please drain out all the water in the unit and 
seal the unit.  Please drain the water from the lowest point of the heat exchanger to avoid 
freezing in winter.  Water recharge and full inspection on the heat pump is needed  before 
it is restarted. 

Check the power supply and the electrical system, make sure the electrical components 
are good, the wiring is tight. 

Don't power off the unit when you use it incontinuity, or the water in the pipe will freeze and 
split the pipe.

6.1 Maintenance

6.Maintenance and repair

26

If the power supply cord is damaged, it must be replaced by the manufacturer or its service 
agent or as imilarly qualified person in order to avoid a hazard.

Steps for replacing the magnesium rod:
Check the state of the magnesium rod half a year according to the above steps and we 
suggest that the magnesium rod should be replaced once a year.
When the diameter of the magnesium rod is less than 5 mm and the length is less than 
100mm, please replace it immediately.
Step 1: Disconnect the power supply, close the water inlet of the unit, and then open the 
water outlet to release the pressure in the water tank till no water come out from the outlet.
Step 2; Open the water drain valve at the bottom of the unit, empty the water tank and 
replace the magnesium rod.
Step 3: After the replacement, close the drain valve, keep the water outlet opened, then 
open the water inlet to fill water to the tank until there is water flow out from the water 
outlet.

6.2  The normal failure and solutions

 For any malfunctions, please refer to the table below :

P01

Top tank water 
temp. Failure

P02

Coil temp. Failure

P04

P05

P07

E01

E02

E03

E04

E07

E08

E09

Ambient 
temp. Failure

Refrigerant absorb 
temp. Failure

High pressure protection

Low pressure protection

Water flow failure

Electric-heater 
overheat protection

Anti-freeze protection

Communication failure

Winter frost protection

P09

Anti-freeze temp. Failure

Bottom water 
temp. Failure

Malfunction

Display

Canse

Solution

The water b

 temp. Sensor 

is open or short circuit

ottom

The water top tank  temp.

 

sensor 

is open or short circuit

The ambient temp.

 

sensor 

is open or short circuit

The pipe temp.

 

sensor is 

open or short circuit

The evaporator temp.

 

Sensor

 is open or short circuit

The exhaust pressure is high ,
 high pressure switch action

The suction pressure is low, 
Low pressure switch action

No water or litter water 
in water system

Wired remote control with master 
signal failure 

Ambient temperature is too low 

Water flow volume not enough,Water 
system pressure difference is small

Water flow volume not enough,Water 
system pressure difference is small

Check or change the water 
bottom  temp. Sensor

Check or change the water 
top tank  temp. Sensor

Check or change the 
ambient temp.

 S

ensor

Check or change the 
pipe temp.

 S

ensor

Check or change the 
evaporator temp.

 

Sensor

Check high pressure switch 
and cooling return circuit

Check low pressure switch and 
cooling return circuit

Check the flow volume ,water 
pump is failure or not

Check the flow volume,water 
system is jammed or not

Check the flow volume,water 
system is jammed or not

The a

Sensor

 is open or short circuit

nti-freeze temp. 

Check or change the 
a

Sensor

nti-freeze temp. 

P034

Solar temp. Failure

Check the connection line between 
the wired remote control and 
motherboard

The solar

Sensor

 is open or short circuit

 temp. 

Check or change the 
solar

Sensor

 temp. 

Содержание AtmosAir 180

Страница 1: ...Operation Installation Manual Operation Installation Manual HEAT PUMP HEAT PUMP ...

Страница 2: ...oduct Please take the time to read it through before operating Once the Installation is complete check that all connections are secure before the power is turned On The installer is to explain to the end user how to operate and maintain the unit in accordance to this Instruction manual If the supply cord is damaged it must be replaced by the manufacturer its service agentor similarly qualified per...

Страница 3: ...tation 9 4 3 installation space 10 4 4 cable connection 12 4 5 trial running 12 5 Usage 13 5 1 function of wire controller 13 5 2 usage of wire controller 15 6 Maintenance and repair 25 7 Appendix 27 6 2 trouble shooting guide 25 6 1 maintenance 25 4 6 seismic restraints 12 27 28 7 1 caution 28 7 2 the method of grounding 29 7 3 use of the Pressure release valve 7 4 drain outthe waterin the storag...

Страница 4: ...ng Compulsory The listed action must be implemented Attention to what is indicated Prohibited Next to this icon The heat pump must be installed by qualified persons Improper installation could result in electrical shock water leakage or fire Please ensure that the unit and power connections have a good earth Failure to do this may cause an electrical shock Professional installer required Earthing ...

Страница 5: ...mportant If the heat pump needs to be relocated or installed again only use an authorised dealer or qualified persons It is prohibited for the end user to repair the unit themselves unless qualified failure to do so may lead to serious injury or and damage to the unit Should the heat pump need to be repaired only use an authorised dealer or qualified persons Prohibited Important OPERATIONATTENTION...

Страница 6: ...hich are unsuitable for solar hot water heating 2 2 Characteristics Easy to operate Featuring an easy to use timer for both start and stop operations with a controller to set the desired water temperature Safe and environmentally friendly Produces no harmful gases along with no open flame making the unit safe to work with when installing Air inlet Air outlet controller tank ...

Страница 7: ...rized vapor is cooled down through the heat exchange with the water in the tank until it condenses into a high pressure moderate temperature liquid Then the pressure of the liqiud refrigerant drops as it passes throttling device Finally refrigerant absorbs heat from the surrounding air and evaporates into vapor with low temperature and low pressure and then it goes into compressor again The cooled...

Страница 8: ...2 4 dimensions Unit mm MODEL ATMOS AIR 180 16 5 1944 5 1277 Cold water inlet Hot water outlet Condensation water outlet Magnesium Over heating protector Electric heater Drainpipe 99 1177 1464 5 Pressure release valve 540 ...

Страница 9: ... the units See package label See nameplate See package label 2 Specifications 2 5 performance parameters 6 Work range 1 Ambient temperature is 0 40 Heat Pump Measurement conditions Instant heating Ambient temperature20 15 Water inlet 15 Water outlet 55 Operating parameters The range of the operating water pressures 0 15 0 7MPa FREEZE PROTECTION The water heater has a freeze protection system The f...

Страница 10: ...n the heating mode the unit will defrost automatically maximizing the heating efficiency Lasting 2 10 minutes The fan motor will stop running whilst the unit is defrosting Water pressure protection temperature or 7 In order to use the unit correctly please run the unit at environment temperature 0 40 The unit includes sophisticated electronic devices prohibited to use water from lake untreated riv...

Страница 11: ...4 internal thread pipes must be heat resistant and durable Installation of the pipe for Pressure release valve The spec of the valve connecting thread is BSP3 4 internal thread After installation it must be confirmed that the drainpipe outlet is exposed in the air drainpipe is joined to the pressure relief orifice of this valve you must ensure that the flexble drainpipe and exposed in the air When...

Страница 12: ...e inclination angle of 60 degree is not exceeded If transport in an inclined position cannot be avoided the unit should be placed into operation one hour after it has been moved into final position Transportation CAUTION High center of gravity WARNING For continued safety of this appliance it mst be installed operated and maintained in accordance with the manufacturer s instructions If the water s...

Страница 13: ...allation space Before installation please ensure that you leave the space as shown below for maintenance Unit mm CAUTION The minimum space of installation is 10 cubic meter 10 Air inlet Air outlet Display Barrier 500 1000 300 ...

Страница 14: ...11 4 Installation Unit mm 1000 500 600 ...

Страница 15: ...ck that all power connections are secure before switching on 4 5 2 Trial running Switch on the unit using the controller In the case of any unusual noise switch the power off and consult your provider If the power cord is damaged It must be replaced by a qualified electrician The parameters have been pre set to a temperature of 60 degrees 4 6 Seismic restraints The unit must be braced with with se...

Страница 16: ... 2 3 4 5 6 ON OFF Mode Electric Heater Up Down Turn on off the unit Switch unit running modes or save setting parameters Set the clock or the timer Turn on off the electric heater or switch fan modes Move up or increase parameter values Move down or decrease parameter values Clock Main display area Auxiliary display area 1 2 3 4 5 6 ...

Страница 17: ...lay area displays the minute Second Shows that the main display area displays the second Centigrade Fahrenheit Parameter setting Shows that the parameter is adjustable Lock Shows that the keyboard is locked Status icon What it means Heating Vacation Shows that the unit is in heating mode Shows that the unit is in vacation mode Eco heating Temperature Shows that the temperature is non adjustable me...

Страница 18: ...ple Intelligent Running interface 5 2 1 Turn ON OFF the unit Press and hold for 0 5s in the standby interface of the wire controller to turn on the unit and at this time the main display area shows the water outlet temperature Press and hold for 0 5s in the running interface of the wire controller to turn off the unit and at this time the main display area shows OFF Note The ON OFF button can only...

Страница 19: ...for 5s the controller exits the parameter modification menu by timeout and the changes are confirmed Setting 75 C When the target temperature is adjusted to 60 C press and hold the for 5s At this time the target temperature is displayed as 61 C and the temperature range changed to 38 75C Press the to set the target temperature to 75 C Example Change the target temperature from 55 C to 70C when the...

Страница 20: ...n press again the hour parameter will flash then press or to change it After making the changes to the parameter press to confirm then change the minute parameter as well as the date parameter in the same way If no operations are performed on the keypad for 10s the controller exits the parameter modification menu by timeout and the changes are confirmed Note Set the date in the same way when in va...

Страница 21: ...the timer1 setting you can set the turn on time of timer2 After finishing the OFF and 2 will flash and then you can set the turn off time of timer2 Press again to save and back to the interface If you don t need to set the timer2 you can press the to save after finishing the timer1 setting You will find the ON and 2 flash No operation for 5s the program will back to the interface automatically Not...

Страница 22: ...into the next setting without confirm the previous one ON 2 Press and hold for 2s to enter into the next setting without confirm the previous one Press and hold for 2s to enter into the next setting without confirm the previous one Press to confirm the time Press to cancel the setting Set the hour Set the minute OFF 2 ...

Страница 23: ...0 20 00 Outlet water temperature Current time Press and hold for 2s ON 1 OFF 1 Press to confirm Successful setting Press to cancel the setting and exit Without saving Confirm the time after setting Confirm the time after setting ON 2 OFF 2 Confirm the time after setting ...

Страница 24: ... flashing at this time Then set the date in the same way as 2 4 Example Set the start up date on September 28 Note Turn off the unit before going out Vacation mode Outlet water temperature The current date ON Press and hold for 0 5s Press then to set the date to September Press then Press to save Press to cancel Month day Press and hold for 2s ...

Страница 25: ... Usage 22 5 2 5 3 If you want to cancel the timer setting follow this below press to cancel all the operation Outlet water temperature Timer state Pressing lasting for 2S The ON and 1 icons are flashing ...

Страница 26: ...top running when the unit target temperature is reached Definition of the fan icon 1 Running shows that the fan is running at high speed 2 Running shows that the fan is running at low speed 3 Fan icon disappears shows that the fan is shut off 4 Static shows that the fan will run at high speed when target setting temperature is reached 5 Static shows that the fan will run at low speed when target s...

Страница 27: ...24 5 Usage 5 2 8 Keyboard locking Press and hold for 5s once to lock the keyboard Press and hold for 5s again to unlock the keyboard Press and hold for 5s Lock icon ...

Страница 28: ...stem make sure the electrical components are good the wiring is tight Don t power off the unit when you use it incontinuity or the water in the pipe will freeze and split the pipe 6 1 Maintenance If the power supply cord is damaged it must be replaced by the manufacturer or its service agent or as imilarly qualified person in order to avoid a hazard Steps for replacing the magnesium rod Check the ...

Страница 29: ...pressure is low Low pressure switch action No water or litter water in water system Wired remote control with master signal failure Ambient temperature is too low Water flow volumenot enough Water system pressure differenceis small Water flow volumenot enough Water system pressure differenceis small Check or change the water bottom temp Sensor Check or change the water top tank temp Sensor Check o...

Страница 30: ...ntact any live electrical part The discharge opening must not be blocked or reduced in size under any circumstances 3 Children should be supervised to ensure that they do not play with the appliance 4 The appliance is fitted with means ford is connection from the supply mains having a contact separation in all poles that provide full disconnection under over voltage category lll conditions and the...

Страница 31: ...e every six months so as to remove the calcium carbonate deposition decrease the temperature Take care as the temperature of the discharging water is very high Vent pipes should be thermally insulated to prevent the pipes freezing in the winter Remark Pressure release valve Model YA 20 action pressure 0 7MPa WARNING Fail to operatethe relief valveeasing gear atleast once everysix months mayresult ...

Страница 32: ...rain outlet loosen the screws and open the cover Press the red button to reset 7 5 Use of the overheating protector DANGER The operation of the thermal cut out indicates a possibly dangerous situation Do not reset the thermal cut out until the water heater has been serviced by a qualified person The overheating protector is used to turn the power off preventing the water from being heated too high...

Страница 33: ...NOTES ...

Страница 34: ...NOTES ...

Страница 35: ...NOTES ...

Страница 36: ...t Industries Registered Office 1 Alan Street Rydalmere New South Wales 2116 Australia Telephone International Sales 61 2 9684 9100 Facsimile International Sales 61 2 9684 9180 Email solahart solahart com au Web www solahart com ...

Отзывы: