Installation Requirements
13
Grounding Requirements
Grounding requirements are as follows:
Ensure that the iSTAR Edge controller is properly connected to an earth ground at the
ground stud in the cabinet. Identified by
symbol.)
Use 16 AWG or larger wire.
Ensure that the shield wires for the readers, inputs, outputs, and AUX cables are grounded
to the nearest earth/ground connection at one end only of the cable.
Disconnect the ground wire last to provide maximum protection to the equipment and
personnel.
NOTE
All cabling must be shielded.