Vertical installation position
Maximum ambient temperatures for mbGate PA
Number of PA
channels used
Maximum
fieldbus voltage
Minimum distance Maximum permissible
ambient temperature T
a
4
32VDC
0 mm
40 °C
2
24VDC
0 mm
45 °C
4
32VDC
17.5 mm
50 °C
2
24VDC
17.5 mm
55 °C
Maximum ambient temperatures for mbGate PB
Number of PA
channels used
Maximum
fieldbus voltage
Minimum distance Maximum permissible
ambient temperature T
a
2
24VDC
0 mm
45 °C
2
24VDC
17.5 mm
55 °C
Maximum ambient temperatures for mbGate DP
Minimum distance
Maximum permissible
ambient temperature T
a
0 mm
45 °C
17.5 mm