ME 3000SP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 48 -
SOFAR technical support.
ID102
BatOV
Battery
high
voltage
protect
ID103
BatUV
Battery
low
voltage
protect
ID104
BatOTD
Battery high temperature
protect while discharging
Make sure battery is in a well-ventilated
place.
Try to decrease the max discharge(A)or/and
max charge(A)to see if the problem is
solved.
ID105
BatOTC
Battery high temperature
protect while charging
ID106
BatUTD
Battery low temperature
protect while discharging
Try to increase the ambient temperature of
the battery.
ID107
BatUTC
Battery low temperature
protect while charging
Maintenance
Inverters generally do not need any daily or routine maintenance.Heat sink should
not be blocked by dust,dirt or any other items.Before the cleaning,make sure that
the DC SWITCH is turned OFF and the circuit breaker between inverter and
electrical grid is turned OFF.Wait at least for 5 minutes before the Cleaning.
Inverter cleaning
Please clean the inverter with an air blower,a dry&soft cloth or a soft bristle
brush.Do NOT clean the inverter with water,corrosive chemicals,detergent,etc.
Heat sink cleaning
For the long-term proper operation of inverters,ensure there is enough space around
the heat sink for ventilation,check the heat sink for blockage(dust,snow,etc.)and
clean them if they exist.Please clean the heat sink with an air blower,a dry&soft
cloth or a soft bristle brush.Do NOT clean the heat sink with water,corrosive