ME 3000SP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 47 -
installed in a well-ventilated place.
3.
Please make sure the inverter is
vertically installed&the ambient temperature
is less than the temperature upper limit of
ME 3000SP
ID82
Over
frequency
AC frequency is too high
ID83
Long dist
Load
Shedding
Long
distance
Load
Shedding
ME 3000SP receives a remote signal to
decrease its power.
ID84
Long dist
OFF
Switch OFF ME 3000SP
remotely
ME 3000SP receives a remote signal to
switch OFF.
ID85
SOC<=1-D
OD
or
Battery
voltage is
low
For example,if you set DOD to 30%,when
SOC is less than 70%,you will see ID85 in
the event list.ME 3000SP won’t discharge
the battery when ID85 is present.
Or
This is an indication of low battery voltage.
ME 3000SP won’t discharge battery in this
case to ensure long battery cycle life.
ID86
Bat Voltage
Low Shut
Battery voltage is too
low&cause ME 3000SP
to switch OFF
ME 3000SP will switch OFF when battery
voltage is too low.This is a protection for
battery.
ID94
Software
version is
not
consistent
Contact SOFAR technical support to
upgrade software.
ID95
CommEEP
ROMFault
The
Communication
board EEPROM is fault
ID95-ID96 are internal faults of ME
3000SP,turn OFF the DC isolator&AC
circuit breaker,wait for 5 minutes,then turn
ON the DC isolator and turn ON the AC
circuit breaker.Check whether the problem is
solved.If no,please contact SOFAR technical
support.
ID96
RTCFault
RTC clock chip is fault
ID98
SDfault
The SD card is fault
Normally ID98 is caused by loose SD card
holder.
Click&take out SD card,press SD card
holder then insert SD card back can
normally solve this problem.
ID99
Wifi fault
The Wifi is error
Just for alarm in factory.
ID100
BatOCD
Battery
over
current
discharging protect
ID100-ID103 is battery fault.If this fault
occurs occasionally,wait few minutes to see
whether the problem is solved.
If this fault occurs frequently,please contact
ID101
BatSCD
Discharging short circuit
protect