ME 3000SP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 27 -
specific country code (AU-VIC, AUSGRID, AU-QLD, AU-SA or AU-WA).
Changing the country code back to 02 AU will disable the Volt-var settings
Note: different distribution network operators in different countries have different
requirements regarding grid connections of battery storage inverters.
Therefore, it’s very important to make sure that you have selected the correct
country code according to requirements of local authority.
Please consult qualified electrical engineer or personnel from electrical safety
authorities about this.
Shenzhen SOFARSOLAR Co.,Ltd. is not responsible for any consequences arising
out of incorrect country code selection.
3)Select battery type
Press“Up”or“Down”to select your battery type,then press“OK”to complete the
battery type setting.
If you’re using“1.PYLON”,“2.DARFON”,“4.General Lithium”,
“5.Alpha.ESS”&“6.SOLTARO”battery types,congratulations,ME 3000SP’s first
time setup is complete.Please press“OK”to enter the main interface.
But if you’re using“3.DEFAULT”battery type.We need more information regarding
your battery.
MENU
Compatible Batteries
1.PYLON
PYLONTECH US2000 PLUS/US2000B
Note:Please confirm with representative of PYLONTECH that your
battery is compatible with ME 3000SP
2.DARFON
DARFON 14S31P ESS
3.DEFAULT
LEAD ACID/LEAD CRYSTAL/AQUION battery
4.General
Lithium
All batteries that comply with SOFAR’S BMS CAN communication
protocol.
5.Alpha.ESS
M48112-P/SMILE-BAT
6.SOLTARO
SL-3KWH/SL-1KWH
4)*Set battery capacity(only for DEFAULT battery type)
Press“Up”or“Down”to change the 1
st
digit,press“OK”to switch to next digit.After
changing the battery capacity per your battery specification,press“OK”,then“Set
max charge voltage”will pop up.
5)*Set max charge voltage(only for DEFAULT battery type)
Press“Up”or“Down”to change the 1
st
digit,press“OK”to switch to next digit.After
changing max charge voltage per your battery specification,press“OK”,then“Set
max charge current”will pop up.
6)*Set max Charge current(only for DEFAULT battery type)