output
ID041
RelayFail
Relay detection failure
ID042
IsoFault
Low insulation
impedance
Check the insulation resistance between
the photovoltaic array and ground
(ground), if there is a short circuit, the fault
should be repaired in time.
ID043
PEConnectFault
Ground fault
Check ac output PE wire for grounding.
ID044
ConfigError
Error setting input
mode
Check the input mode
(parallel/independent mode) Settings for
the inverter. If not, change the input mode.
ID048
SNTypeFault
Serial number fault
Internal faults of inverter, switch OFF
inverter, wait for 5 minutes, then switch ON
inverter. Check whether the problem is
solved.
If no, please contact technical support.
ID050
TempFault_HeatS
ink1
Radiator 1 temperature
protection
ID057
TempFault_Env1
Ambient temperature 1
protection
ID059
TempFault_Inv1
Module 1 temperature
protection
ID065
VbusRmsUnbalan
ce
Unbalanced bus
voltage RMS
Internal faults of inverter, switch OFF
inverter, wait for 5 minutes, then switch ON
inverter. Check whether the problem is
solved.
If no, please contact technical support.
ID066
VbusInstantUnbal
ance
The transient value of
bus voltage is
unbalanced
ID072
SwBusRmsOVP
Inverter bus voltage
RMS software
overvoltage
ID073
SwBusInstantOVP
Inverter bus voltage
instantaneous value
software overvoltage
ID082
DciOCP
Dci overcurrent
protection
ID083
SwOCPInstant
Output instantaneous
current protection
ID085
SwAcRmsOCP
Output effective value
current protection
ID086
SwPvOCPInstant
PV overcurrent
software protection
ID098
HwBusOVP
Inverter bus hardware
overvoltage
ID102
HwPVOCP
PV hardware overflows
ID103
HwACOCP
Ac output hardware
overflows