7.Trouble shooting and
maintenance
7.1. Troubleshooting
This section describes the potential errors for this product. Please read carefully
for the following tips when doing the troubleshooting:
1) Check the warning message or faulty codes on the inverter information panel
2) If not any error code display on the panel, please check the following lists:
—
Is inverter be installed in a clean, dry, ventilated environment?
—
Is the DC switch turn off?
—
Are the cable cross section area and length meet the requirement?
—
Are the input and output connection and wiring in good condition?
—
Are the configuration settings correctly for the particular installation?
This section contains the potential errors, resolution steps, and provide users with
troubleshooting methods and tips
The process to check the event list can refers to Manual Chapter 7.3 (B)
List7-1 Even list
Code
Name
Description
Solution
ID001
GridOVP
The grid voltage is too
high
If the alarm occurs occasionally, the
possible cause is that the electric grid is
abnormal occasionally. Inverter will
automatically return to normal operating
status when the electric grid’s back to
normal.
If the alarm occurs frequently, check
whether the grid voltage/frequency is
within the acceptable range. If yes, please
check the AC circuit breaker and AC wiring
of the inverter.
If the grid voltage/frequency is NOT within
the acceptable range and AC wiring is
correct, but the alarm occurs repeatedly,
ID002
GridUVP
The grid voltage is too
low
ID003
GridOFP
The grid frequency is
too high
ID004
GridUFP
The grid frequency is
too low