SOFAR 25~50KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 60 -
can check the current software version in Systemlnfo>>3.SoftVersion.
Note:
If screen shows
“
Communication fail
”
,
“
Update DSP1 fail
”
,
“
Update
DSP2 fail
”
please turn off the DC switch, wait for the LCD screen turn off, then
turn on the DC switch again, then Continue to update from step 5.
6.5. Smart meter instruction
Generation and Export Limit Control functions for the inverter are available
but require the use of an external measurement device to obtain grid information.
Step 1:
In the standard interface, Long press DOWN button to enter the "1. Enter
Setting" interface, and then Short press DOWN button to enter "13.PCC Select"
interface, long press DOWN button to confirm the input password (initial password
is 0001), press up or down to find "PCC Meter", and then long press DOWN button
to display "14.Reflux Mode". In the "Anti-Reflux Mode" (14.Reflux Mode) interface,
select one of the CTR Totalpower, CTR Phasepower, or CTR SellingPower by press
DOWN button, ."success" will be displayed if setting successfully.
Step 2:
In the standard interface, Long press DOWN button to enter the "1. Enter
Setting" interface, and then Short press DOWN button to enter the "10. Set
AntiReflux" interface, long press DOWN button to confirm the input password
(initial password is 0001), the power setting can be entered by pressing the UP or
DOWM button to find the "Reflux Enable", and Long press the DOWM button for
confirmation; Press the up or DOWM button to change the size of the value, and
then long press the DOWM button to complete the input of the current value, and
enter the setting of the next value. After setting the fourth number, long press the
DOWM button to confirm, the value selection of antiReflux power can be
completed.
Note: Explanation of professional terms:
CTR Totalpower:The Sum of three-phase selling power of the connection point <=
The set Reflux power