SOFAR 25~50KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 26 -
Figure 4-2 Grounding connection instruction
(
1
)
Note
:
the length of L2 should 2~3mm higher than L1
Step 2
: Insert the exposed core wires into the OT terminal and crimp them by using
a crimping tool, as shown as figure 5.3. Recommend using OT terminal: OT-M6.
Figure 4-3 Grounding connection instruction
(
2
)
Note 1:
L3 is the length between the insulation layer of the ground cable and
crimped part. L4 is the distance between the crimped part and core wires
protruding from the crimped part.
Note 2:
The cavity formed after crimping the conductor crimp strip shall wrap the
core wires completely. The core wires shall contact the terminal closely.
Step 3:
Tighten the OT terminal by using M6 screw. Recommend torque is 5-7N.m
M6 screw
OT
terminal
Threaded hole