SOFAR 3.3~12KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 29 -
RNBL5-4 (10-12awg).
terminal shall not be exposed.
Figure 4- 8 AC cable connection instruction diagram (1)
Step 2:
After assembling the PG waterproof connector, connect the cable to the
AC terminal block L1, L2, L3, N, PE contacts, and fasten them (1~1.6 N · m).
Tighten the lock nut of PG terminal clockwise (5~5.5 N · m).
Figure 4- 9 AC cable connection instruction diagram (2)
4.4. Connect PV side of inverter (DC-Input)
DC Switch is a model of the following specifications or equivalent, subject to
CEC certification number.
Inverter model
Model of DC switch
SOFAR 3.3KTLX-G3
SOFAR 4.4KTLX-G3
SOFAR 5KTLX-G3-A
SOFAR 5.5KTLX-G3
SOFAR 6.6KTLX-G3
SOFAR 8.8KTLX-G3
SOFAR 11KTLX-G3
XBHP+3319-ADA/6(TUV AZ 69025024 meets
AS60947.3:2018
The AS/NZS IEC60947 standards)
SOFAR 8.8KTLX-G3-A
SOFAR 10KTLX-G3-A
SOFAR 11KTLX-G3-A
SOFAR 12KTLX-G3
XBHP+3419-AAX/6(TUV AZ 69025024 meets
AS60947.3:2018
The AS/NZS IEC60947 standards)