arising out of incorrect country code selection.
If the inverter indicates any fault, please refer to Section 7.1 of this manual ——
trouble shooting for help.
5.3. Shutdown inverter
Step 1: Turn OFF the AC circuit breaker.
Step 2: Turn OFF the DC switch.
5.4. Setting power quality response modes
Once the power quality and grid settings have been selected at commissioning,
these settings will be locked, end customers cannot modify by themselves. These
setting require professional and technical personnel to conduct them by issuing
and transmitting instructions on the remote monitoring platform, on the premise
that the logger is installed (WiFi/GPRS/Ethernet). And the account must be
authorised by SOFARSOLAR.
Power quality settings can be set/view/changed by logging onto
solarmanpv.com.
Access to solarmanpv.com is restricted to authorised personnel only (refer to
Section 4.5.3 for instructions on accessing solarmanpv.com).
An account must be created to use solarmanpv.com.
Technical personnel can send control instructions on the monitoring page to
modify the mode and parameters of the machine, and the corresponding
instructions need to be provided by internal professionals.
Once set chosen country grid code has been selected, the current inverter
settings, including firmware version can be viewed under the “System Info”
menu. Please refer to section 6.3 Main Interface.