SOFAR 3.3~12KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 50 -
002-008 Australia B (Australia Region B)
002-009 Australia C (Australia Region C)
Please contact your local grid operator for which option to select
Note: By selecting 002-000 Australia A, 002-008 Australia B or 002-009
Australia C the power quality response mode and grid protection settings will be
reset to their default values for Australia Region A, B, C respectively.
Default grid settings for different regions are shown in the following table:
Protective function
Protective function
limit
Trip delay time
Maximum
disconnection time
Undervoltage 2(V<<)
70V
1s
2s
Undervoltage 1(V<)
180V
10s
11s
Overvoltage 1(V>)
265V
1s
2s
Overvoltage 2(V>)
275V
-
0.2s
Region
Australia A
Australia B
Australia C
New Zealand
Under-
frequency 1
(F<)
Protective
function limit
value
47Hz
47Hz
45Hz
45Hz
Trip
delay
time
1s
1s
5s
1s
Maximum
disconnection
time
2s
2s
6s
2s
Over-
frequency 1
(F>)
Protective
function limit
value
52Hz
52Hz
55Hz
55Hz
Trip
delay
time
-
-
-
-
Maximum
disconnection
time
0.2s
0.2s
0.2s
0.2s
Default volt-watt settings for different regions are shown in the following table:
Region
Default value
V
L2
V
L1
V
W1
V
W2
Australia A
Voltage
207
215
253
260
Inverter output (P) % of
S
rated
20%
100%
100%
20%
Australia B
Voltage
195
215
250
260
Inverter output (P) % of
S
rated
0%
100%
100%
20%
Australia C
Voltage
207
215
253
260