background image

MASTERYS IP+

60-80 kVA 3/3

IT

ALIANO

ENGLISH

54

   IOMMASIPXX08-GB  02

For parallel 1+1 redundant confi guration only.
Parallel confi guration must only be activated by SOCOMEC UPS qualifi ed personnel.

Use the UPS in accordance with the technical specifi cations given in this Installation and Operating Manual.
The UPS units connected in parallel confi guration are identical to a standard UPS, as a result safety, shipping and 
installation recommendations in chapters 2 and 3 also apply.

INSTALLATION.

UPS units operating in parallel are interconnected using control cable 

A

 and 

are confi gured diff erently depending 

on the position they are assigned. For this reason the units have a position label:
The “LEFT” label means that the unit must be positioned to the left (UPS with transformer confi gured as concentrator);
•  The “RIGHT” label means that the unit must be positioned to the right (UPS without transformer).

The control cables supplied allow a maximum distance of about 3 metres between the UPS units. This gives enough 
room for an external battery cabinet to be inserted beside each UPS.

POWER CONNECTIONS.

•  The power supply to each unit must be protected as indicated in the table in paragraph 3.4.
•  The cross section and length of the input and output cables must be identical for all the units. 
•  The phase rotation must be the same for both unit connected in parallel.
•  Cables of the same length and cross section must be used for the connection between the general power switch 

1

the switches 

3

 and the respective UPS units.

•  If a diff erential switch is installed on the mains power switch (optional), it must be inserted upstream from the 

distribution panel, it must be a selective type and 

the trigger value must be 0.5 A by the number of UPS con-

nected in parallel

.

CONTROL CONNECTIONS.

In order for units connected in a parallel confi guration to operate correctly, control cables are required to exchange 
data between the various UPS units making up the parallel system, for management of correct load sharing and 
synchronisation logic.
The cables in question are supplied with the UPSs.

Parallel confi guration must only be activated by SOCOMEC UPS qualifi ed personnel

; in each case arrange the 

running of the control cables in the relative cable run as shown in fi gure 2 leaving the connectors unconnected.

PARALLEL 1+1 REDUNDANT CONFIGURATION

Содержание MASTERYS IP+ 60

Страница 1: ...INSTALLATION AND OPERATING MANUAL MASTERYS IP 60 80 kVA 3 3...

Страница 2: ......

Страница 3: ...lation transformer 16 3 10 ADC card with temperature sensor 17 3 11 External battery cabinet connection 19 4 MODES OF OPERATION 20 4 1 ON LINE operations 20 4 2 Operation in high efficiency mode 20 4...

Страница 4: ...nication 36 9 2 Standard Lan web page 37 9 3 Accessories and SW options 44 10 PROBLEM SOLVING 46 10 1 System alarms 46 10 2 UPS Alarms 46 10 3 Preventive maintenance 48 11 OPTIONS 49 11 1 Kit GSS Glob...

Страница 5: ...pply applied load batteries Insufficient or inadequate maintenance Attempted maintenance repairs or modifications not carried out by SOCOMEC UPS personnel or personnel from a support centre authorised...

Страница 6: ...nces Connect the PE ground conductor first before you make any other connection Do not expose the UPS to rain or liquids in general Do not introduce external bodies If the UPS is not equipped with aut...

Страница 7: ...property the products may have to be adapted For such uses we would advise you to contact SOCOMEC UPS beforehand to confirm the ability of these products to meet the requested level of safety performa...

Страница 8: ...pment and break ing devices to ensure that the unit does not fall over 3 1 SHIPPING AND MOVING The UPS must remain in a vertical position during all shipping and moving operations Ensure that the floo...

Страница 9: ...80 kVA 3 3 ENGLISH IOMMASIPXX08 GB 02 9 3 UNPACKING AND INSTALLATION OFTHE UNIT 3 2 UNPACKING PROCEDURE 3 2 1 3 2 2 C Secure the UPS to the floor by using the suitable holes C provided see picture 3...

Страница 10: ...sources of excessive heat A space of at least 40 cm must be left at the back for adequate ventilation see figure 3 3 1 The UPS switches are accessed from the front however a space of at least 1 5 metr...

Страница 11: ...ientovervoltages adequateexternalprotectionsmustbeinstalled Size of the input protection devices UPS Magneto thermal Magneto thermal Differential Input Output Battery Battery input 1 AuxMains 1 input...

Страница 12: ...talled as close as possible to the UPS For further information on the connection and the type of remote switch please refer to paragraph 11 7 of this manual ATTENTION The neutral is not disconnected a...

Страница 13: ...the system and wait for 5 minutes before working on the terminal board or any internal UPS parts Legend A Mimic panel B Fans C Fan fuses D Power connections E Slot for optional cards F SerialRS232 48...

Страница 14: ...he power supply open the external battery cabinet disconnectors isolate the system and wait 5 minutes For the power connections to the connecting bars use cables with tinned eyelets only 3 6 1 3 6 4 M...

Страница 15: ...NSFORMER L12 L22 L32 N2 MAINS SUPPLY L2 L3 N OUT TRANSFORMER AUX MAINS SUPPLY L14 L24 L34 N4 L11 L21 L31 N1 B2 B2 B1 B1 EXT BATTERY TA4 TA5 L1 L2 L3 N L11 L21 L31 N 95 120 mm2 TO LOAD L1 IN TRANSFORME...

Страница 16: ...ntial contact to terminals IN1 and IN1 of the ADC card 3 9 ISOLATIONTRANSFORMER The MASTERYSTM IP model of the MASTERYSTM range is fitted with an internal isolation transformer If an external isolatio...

Страница 17: ...S D 1 OFF OFF In 2 Supply from GenSet 1 OFF OFF In 3 Isolation controller 2 Mode 2 POWER SAFE configuration Position IN OUT Description Filter dip1 dip2 level ON OFF Out 1 General Alarm 2 ON OFF Out 2...

Страница 18: ...on loop closing Description of signals Message on the mimic panel General Alarm Battery discharging Battery Low or Imminent stop UPS on bypass E S D Supply from GenSet Isolation controller Power safe...

Страница 19: ...rt service Cabling errors with inversion of the battery polarity may cause permanent damage to the equip ment Replace the terminal board s protection If using cabinets not supplied by the manufacturer...

Страница 20: ...maintain or recharge the battery Bypass mode In case of inverter failure the load is automatically transferred onto the auxiliary mains without any interruption in the power supply This procedure may...

Страница 21: ...erter contributes to compensate the re injected harmonics 4 3 OPERATIONWITH MANUAL MAINTENANCE BYPASS If the maintenance bypass is activated using the appropriate procedure the load is powered directl...

Страница 22: ...normal operation of the UPS for a continuous power supply to the load Position 0 OFF this completely isolates the UPS output by removing the voltage from the applications in any operating condition I...

Страница 23: ...identifies the condition of the power supply to the load C alphanumeric information that uses a menu layout to provide details on any alarms that may occur and on the measurements controls and param...

Страница 24: ...y capacity Steps of 25 Battery recharging Sequence M7 M4 M8 Inverter on Steady Inverter general alarm Flashing M9 Switch Q3 closed and output voltage present Steady M10 Input mains OK Steady Input mai...

Страница 25: ...in progress GREEN Load powered from inverter or in high efficiency mod 6 3 MEANING OFTHE LUMINOUS BAR The luminous bar figure 6 1 1 provides an immediate indication of the condition of the power supp...

Страница 26: ...STICS 3 COMMANDS 3 1 IMMEDIATE COMMANDS 3 2 EXTENDED COMMANDS 4 PARAMETERS 4 1 PRESENT CONFIG 4 2 PRESENT DATA 5 SERVICE 5 1 COMMISSIONING 5 2 SETTING 5 3 SERVICE CODE 6 HYSTORY 6 1 HISTORY LOG 1 ALAR...

Страница 27: ...he operations indicated on the mimic panel 7 2 SHUTDOWN Shutdown interrupts the power supply to the load and causes the UPS and the battery charger to stop Activate the procedure COMMANDS IMMEDIATE CO...

Страница 28: ...TURNTO NORMAL MODE Put switch Q2 into position 1 mains ON Wait for the mimic panel to switch on Activate the procedure COMMANDS IMMEDIATE COMMANDS START PROCEDURE Carry out the operations indicated on...

Страница 29: ...GER GENERAL ALARM Battery charger fault A29 BYPASS GENERAL ALARM Bypass fault A30 STOP FOR OVERLOAD The duration of the overload has inhibited the bypass A32 MODULE 1 GENERAL ALARM Module 1 failure A3...

Страница 30: ...a programmable reference period has been defined the system reports measurements that are made avail able in digital or graphical format The values that are represented graphically can be used to ana...

Страница 31: ...ass and shutdown of the UPS PROCEDURE HIGH EFFICIENCY MODE Activates Eco mode always on mode NORMAL MODE Activates normal double conversion operation ALARM RESET Resets all the alarms LEDS TEST Perfor...

Страница 32: ...0000 Identifie the mac addres of LAN PCB DSP RV 000 CKS 0000 8 5 SERVICE MENU This is used to change the configuration parameters insert the warranty activation code and display the service code 8 5 1...

Страница 33: ...BER OF MODULES Only appears in case of parallel systems 1 2 Indicates the number of UPSs in the system REDUNDANCY LEVEL Only appears in case of parallel systems FROM 0 TO THE NUMBER Indicates the numb...

Страница 34: ...ress of the LAN 255 255 255 255 XXX XXX XXX XXX SERIAL LINK JBUS Sets the mimic panel jbus node 1 15 SLAVE NUMBER DATE AND TIME Sets the date and time DD MM YY HH MM EXTENDED COMMAND Enables Disables...

Страница 35: ...d rapid diagnostic of the problem In the event of a fault select the menu SERVICE SERVICE CODE and inform the support centre of the code displayed 8 5 3 1 8 7 MIMIC PANEL CONCENTRATOR In systems with...

Страница 36: ...signalling and remote monitoring See the options paragraph to access the detailed functions of the PCBs installed in the slots Please note that two NetVision cards or two GSS cards cannot be connecte...

Страница 37: ...se the procedure indicated below is only valid if using a stand alone PC i e not in a network of computers with admin istrator privileges and a network twisted cable Deactivate DHCP mode in the COMMAN...

Страница 38: ...available The main web page shows the general status of the UPS This page like all the sub pages are dynamic i e the data images or type of messages shown vary in accordance with the UPS status and co...

Страница 39: ...OMEC group publishes on the site so as to take full advantage of the MASTERYSTM unit UPS information Serial number type power etc Alarm present shows the alarms table this icon appears when the UPS de...

Страница 40: ...tive flag to choose a different language If the desired language is not listed see if it is downloadable from the www socomec com web site Refer to the chapter on software updating for instructions on...

Страница 41: ...k will be able to access the supervisor one client at a time If the address 255 255 255 255 is inserted access will be denied to all users Software updating if on allows the supervisor to be updated P...

Страница 42: ...igure the parameters of a modem Rings before reply Setthenumber ofringsafterwhichthemodemshould respond Outgoing call1 sets the type of outgoing call SMS or E service to activate e service a contract...

Страница 43: ...e 9 2 2 11 System Information Area This area of the screen page shows the measurements and the UPS op erating mode Click on icon A to display the input measurements Click on icon B to display the bat...

Страница 44: ...k re sources The physical position of the UPS is not significant The main functions are 10 100Mb Ethernet connection RJ45 Graphic monitoring of the UPS via web browser Remote shutdown of up to 40 comp...

Страница 45: ...is via modem free air GSM or ANALOG fixed line The auto diagnostic system analyses UPS operating conditions identifies faults and monitors environmental conditions such as temperature overload avoidin...

Страница 46: ...s variations typical with power supplied from an incorrectly sized GE A07 temperature over the limits The technical plant temperature is higher than the maximum value recommended Check the ventilation...

Страница 47: ...ad rate applied to the UPS and reset the alarms A42 T Service general alarm The MASTERYS products can be remotely serviced This alarm indicates that a procedure for analysing the UPS failure has been...

Страница 48: ...tery MASTERYS stores statistics on the conditions of use of the battery for analysis Since the expected life of the batteries is very much dependent on operating conditions number of charging and disc...

Страница 49: ...ph 3 9 ADC card 11 3 REMOTE MIMIC PANEL This device monitors and interacts with the UPS through a serial link RS 485 maximum distance of 175 m 25 m cable supplied standard 50 m cable available as an o...

Страница 50: ...Activating UPS protection on the mimic panel access the Configuration menu on the mimic panel see the Con figuration Menu section in the manual and set the BACKFEEDTYPE parameter to 2 BYPASS INPUT Alo...

Страница 51: ...is used Nominal power kW 48 64 Overload on mains power supply 125 10 minutes 150 1 minute Crest factor 3 1 Voltage distortion 1 with linear load Pout 90 Pnom Environment 60 80 Operating temperature 0...

Страница 52: ......

Страница 53: ...PARALLEL 1 1 REDUNDANT CONFIGURATION MASTERYS IP 60 80 kVA 3 3...

Страница 54: ...serted beside each UPS POWER CONNECTIONS The power supply to each unit must be protected as indicated in the table in paragraph 3 4 The cross section and length of the input and output cables must be...

Страница 55: ...Main differential magneto thermal switch 2 Parallel bus cable 3 Magneto thermal switch 4 Output switch 5 System shutdown switch 6 Distribution 7 UPS with transformer 8 UPS without transformer 9 Power...

Страница 56: ...ORMER IN TRANSFORMER MAINS SUPPLY EXT BATTERY AUX MAINS SUPPLY L14 L24 L34 N4 L11 L21 L31 N1 B2 B2 B1 B1 L1 L2 L3 N OUTPUT MAINS SUPPLY EXT BATTERY AUX MAINS SUPPLY L14 L24 L34 N4 L11 L21 L31 N1 B2 B2...

Страница 57: ......

Страница 58: ......

Страница 59: ......

Страница 60: ...mec com UNITED KINGDOM Cirencester GL7 5XL Tel 44 0 1285 863300 info ups uk socomec com OTHER COUNTRIES Tel 34 935 407 575 info ups europe socomec com IN EASTERN EUROPE MIDDLE EAST AFRICA UNITED ARAB...

Отзывы: