MENU
8
8.1 “ALLARMS” MENU
This is used to display all the alarms that are active at the time of access.
The alarms menu is activated automatically when an alarm condition occurs.
ALARMS menu
Code
Mimic panel description
Meaning
A00 GENERAL
ALARM
A01
BATTERY ALARM
Battery circuit failure or faulty operation.
A02
OUTPUT OVERLOAD
Power required in output over the limits.
A06
AUXILIARY MAINS OUT OF TOLERANCE
The voltage or frequency limits accepted by the bypass have been
exceeded.
A07
OVER TEMPERATURE
Temperature excessive or ventilation problems.
A08
MAINTENANCE BYPASS ACTIVE
Q5 in position 1.
A17
IMPROPER CONDITION OF USE
Improper conditions of use verifi ed (load, mains, and temperature).
A18
BLOCKING INVERTER FOR OVERLOAD
Inverter shutdown due to overload.
A20
WRONG CONFIGURATION
Error in the confi guration parameters (e.g. diff erent parameters
between several UPSs in parallel).
A22
INPUT MAINS OUT OF TOLERANCE
The voltage or frequency limits accepted by the rectifi er have been
exceeded.
A23
RECTIFIER GENERAL ALARM
Rectifi er fault.
A25
INVERTER GENERAL ALARM
Inverter fault.
A26
BATTERY CHARGER GENERAL ALARM
Battery charger fault.
A29
BYPASS GENERAL ALARM
Bypass fault.
A30
STOP FOR OVERLOAD
The duration of the overload has inhibited the bypass.
A32
MODULE 1 GENERAL ALARM
Module 1 failure.
A33
MODULE 2 GENERAL ALARM
Module 2 failure.
A38
EXTERNAL ALARM 1
Signalling from ADC input.
A39
EXTERNAL ALARM 2
Signalling from ADC input.
A40
EXTERNAL ALARM 3
Signalling from ADC input.
A41
EXTERNAL ALARM 4
Signalling from ADC input.
A42
E-SERVICE GENERAL ALARM
Alarm that generates automatic sending of a signal to the support
centre (if the service has been activated).
A43
REDUNDANCY LOST
The power required by the load no longer allows the preset
redundancy N+x to be maintained (for UPSs in parallel only).
A44
PERIODIC SERVICE CHECK-UP
Warning for periodic check by support service.
A47
MAX BATTERY TEMPERATURE
Control of the temperature of battery cabinet.
A49
BATTERY DISCHARGED
The energy available in the battery has been used up.
A51
OPTION BOARD GENERAL ALARM
Fault related to the optional PCBs in the slots.
A56
GENERATOR SET GENERAL ALARM
Minor alarm on generator set.
A57
GENERATOR SET FAULT
Major alarm on generator set.
A58
E.S.D. ACTIVATED
The remote emergency shutdown command has been activated.
A59
BATTERY CIRCUIT OPEN
The battery switch is open.
A60
FAN FAILURE
Fans faulty or blocked.
A61
PHASE ROTATION FAULT
Wrong phase cycle direction.