MASTERYS IP+
60-80 kVA 3/3
ENGLISH
IOMMASIPXX08-GB 02
33
Once the code is obtained, enter it by pressing
ENTER
to activate the entry (two asterisks will appear). Select the
fi rst character with the
UP
and
DOWN
keys and confi rm with
ENTER
to accept the character. Then move
on to the next character. Pressing the
ENTER
key after selecting the fourth character activates code.
SEE INSTALLATION MANUAL
FOR PROCEDURE
CODE = - - - - **
An error message is displayed if the code is incorrect.
Check that the code displayed corresponds to the one provided by the Support Centre and repeat the procedure.
8.5.2 “Present confi gurations” menu.
This is used to change the confi guration parameters.
Press
ENTER
.
Access is via the password
MAST
which is keyed in by using the
UP
and
DOWN
keys and
ENTER
to go on to the next letter.
Note.
Column A shows whether the parameter is visible in the
PARAMETERS “CONFIGURATIONS”
menu.
PRESENT CONFIGURATIONS menu
A Parameter
Description
Allowed values
LANGUAGE SELECTION
Selects the required language
DE-EN-ES-FR-IT,
other languages on request
• NUMBER OF MODULES
Only appears in case of parallel systems.
1-2
Indicates the number of UPSs in the system.
• REDUNDANCY LEVEL
Only appears in case of parallel systems.
FROM 0 TO THE NUMBER
Indicates the number of redundant UPSs.
OF MODULES LESS ONE
• OUTPUT VOLTAGE
Sets the required output voltage value.
208/220/230/240
• OUTPUT FREQUENCY
Sets the required output frequency value.
50/60
• CONVERTER
Sets whether the UPS has to operate as a frequency
YES/NO
converter.
WARNING!
Set
only
on UPS with mains power (MAINS) and auxiliary mains (AUX MAINS) separated
and with the auxiliary mains (AUX MAINS)
disconnected!
Do not set
on UPS with common mains lines as it could
damage the load!
• AUTO ON
Sets whether the UPS has to restart automatically after
YES/NO
shutdown due to minimum battery level.
BATTERY AVAILABLE
Indicates whether the batteries are present
YES/NO
BATTERY TEMP. PROBE
Indicates if the battery sensor is present
ENABLE/DISABLE
• BATTERY TYPE
Selects the type of batteries used
SEALED, OPEN VENT, NI-CD
• BATTERY RECHARGE
Selects the type of recharge required
AUTO, MAINTENANCE,
2
LEVELS,
INTERMITTENT
• BATTERY CAPACITY
Sets the battery capacity in Ah.
6,50 ÷ 1.000 (x number of UPS)
• BATTERY ELEMENTS
Indicates the number of elements in series
114÷132
in
a
branch.
MENU
8