23
ENGLISH
MASTERYS
BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
5. MIMIC PANEL
5.1.5. Measurements
menu
This menu is used to display all measurements relating to UPS input, output, and the battery. For models with single phase input or output,
the voltage and current displays are adjusted automatically.
MEASUREMENTS menu
Type of measurements
Value
Value
Value
Note
OUTPUT VOLTAGE
___ V
___ V
___ V
Output voltage
OUTPUT LOAD
__ %
__ %
__ %
Output load percentage
OUT ACTIVE PWR
__._ kW
Output active power
OUTPUT FREQNCY
__._ Hz
Output frequency
AUX VOLTAGE
___ V
___ V
___ V
Auxiliary mains voltage
AUX FREQUENCY
__._ Hz
Auxiliary mains frequency
INPUT VOLTAGE
___ V
___ V
___ V
Input mains voltage
INPUT FREQUENCY
__._ Hz
Input mains frequency
BATTERY VOLTAGE
B+___ V
B+___ V
Battery voltage
CAPACITY
__ %
Battery capacity percentage during charging
BACKUP INFO
T___MIN
Backup time during battery discharge
INTERNAL TEMP.
__ °C
Internal temperature
5.1.6. Commands
menu
This is used to send immediate commands for start-up/shutdown/reset alarms to the UPS and to select the operating mode.
Commands can also be sent for diagnostic purposes by means of the extended commands menu (if enabled in the configurations
menu). The command is activated by selecting it with the
and
keys, press
ENTER
, confirm
YES
or
NO
, then press
ENTER
.
IMMEDIATE COMMANDS menu
Command
Description
START PROCEDURE
UPS start-up command
STOP PROCEDURE
UPS shutdown command
HIGH EFF. MODE
High effi ciency mode: activates the energy saving feature
NORMAL MODE
Activates normal double conversion operation
ALARMS RESET
Resets all the alarms
LEDS TEST
Performs test on mimic panel LEDs
EXTENDED COMMANDS menu
Command
Description
BATTERY TEST
Activates the battery test to check battery effi ciency
BATT.COMMISSION
Activates forming charging for the battery
CHECK-UP DISAB.
Disables the regular maintenance message
5.1.7. Parameters
menu
Displays the UPS parameters set.
UPS CURRENT DATA menu
Message
Description
MASTERYS 3/3 30 KVA
SN. 0000000000
Displays the size, input and output phase confi guration and UPS serial number
UC FW. REVISION
RV 000 CKS: 0000
Identifi es the microprocessor software release
DSP FW. REVISION
RV 000 CKS: 0000
Identifi es DSP software release