6
MASTERYS
BC 60-80 kVA - Ref.: IOMMASBCXX06-EN 06
The packaging guarantees the stability of the UPS during shipping and physical transfer. Carry the packaged unit as close as possible
to the installation site.
When moving the unit on even slightly sloping surfaces, use the blocking equipment and braking devices to ensure
that the unit does not fall over.
2.1. SHIPPING AND MOVING
• The UPS must remain in a vertical position during all shipping and moving operations.
• The unit has wheels that can be used to move it for short distances.
• Ensure the floor is strong enough to support the weight of the UPS and battery cabinet, if used.
Avoid pressing on the front panels when moving the unit.
The UPS MUST only be moved by two people at least. They MUST take position at the sides of the UPS with
respect to the direction of movement.
CAUTION IF DAMAGED
NON-SPILLABLE BATTERIES
If packaging is crushed, ripped or open such that the inner contents are revealed, the equipment should be kept in
an isolated area and inspected by a qualified person. If the packaging cannot be shipped the contents should be
collected promptly, kept apart, and the sender or recipient should be contacted.
All packaging must be recycled in compliance with existing legislation in the country where the system is installed.
2. UNPACKING AND INSTALLATION OF THE UNIT
2.2. ENVIRONMENTAL
REQUIREMENTS
• The recommended operating temperature, humidity and altitude values are listed in the technical specifications table (see chapter 10).
Cooling systems may be required to maintain these values.
• Avoid dusty environments or areas where there is dust from conductive or corrosive materials (e.g. metal dust or chemical solutions).
• The UPS is not designed for outdoor use.
• Do not expose the UPS to direct sunlight or sources of excessive heat.
• A space of at least 40 cm must be left at the back for adequate ventilation (see figure 2.2-1).
• The UPS switches are accessed from the front; however, a space of at least 1.5 metres should be left at the front of the UPS for
maintenance purposes. It is also advisable to ensure that the cable connections are sufficiently long and flexible so that the unit
can be extracted during maintenance (see figure 2.2-2).
• If it is not possible to leave sufficient space at the front, adequate access must be ensured from both sides.
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS
40 cm
1,5 m
UPS
40 cm
1,5 m
20 cm
20 cm
2.2-1
2.2-2