Special precautions
• The unit is heavy: wear safety shoes and preferably use a vacuum lifter for
handling operations.
• All handling operations will require at least two people (unpacking, lifting,
installation in a rack system).
• Before and after the installation, if the UPS remains de-energised for a long
period, the UPS must be energised for a period of 24 hours, at least once every
6 months (for a normal storage temperature under 25°C). This charges the
battery, thus avoiding possible irreversible damage.
• During the replacement of the Battery Module, it is imperative to use the same
type and number of elements as the original Battery Module provided with the
UPS to maintain an identical level of performance and safety.
Note:
this is a category C2 UPS product. In a residential environment,
this product may cause radio interference, in which case the user may be
required to take additional measures.