5.2 POWER AND BYPASS MODULE INSERTION
Note!
Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
WARNING! RISK OF TIPPING OVER!
Before carrying out any operations, ensure the UPS is secured at the feet.
WARNING! RISK OF TIPPING OVER!
The six feet must be secured evenly to ensure the unit is stable.
WARNING! RISK OF TIPPING OVER!
The modules must be inserted from the bottom upwards and removed from the top downwards
to ensure the unit remains stable.
WARNING!
Before removing any module, ensure that the remaining power modules can support the load.
Power module electrical diagram
Bypass module electrical diagram
X2
F1/F2
80 A
F3/F4/F5
80 A
F6/F7/F8
80 A
400 Vac 3ph+N 50 Hz
+/-400 Vdc 3 W
400 Vac 3ph+N 50 Hz
X1
X1
INPUT BATTERY
INPUT MAINS
UPS OUTPUT
AUXILIARY MAINS
UPS OUTPUT
400 Vac 3ph 50 Hz
400 Vac 3ph 50 Hz
X3