4.3.2. TR split-core current sensors
The TR split-core current sensors are used to set up measurement points in a new or existing installation without
HMSDQEDQHMFVHSGHSRB@AKHMF3G@MJRSNSGDRODBHjBKHMJSGDX@QDQDBNFMHRDCAXSGD#(1(2!@MCSGDNUDQ@KK@BBTQ@BX
of the measurement chain is guaranteed.
4.3.2.1. Range
Four models are available from 25A to 600A to analyse several types of loads.
TR-10
TR-16
TR-24
TR-36
Cable
passage
diameter
10mm
16mm
24mm
36mm
Nominal
current
range In
25 - 75 A
32 - 100 A
63 - 200 A
200 - 600 A
Actual
range
0.5 - 90 A
0.64 - 120 A
1.26 - 200 A
4 - 720 A
Maximum l
90A
120A
240A
720A
Reference
4829 0551
4829 0552
4829 0553
4829 0554
4.3.2.2. Dimensions
P
A
L
Ø W
C
B
H
Dimensions
in
/mm
TR-10
TR-16
TR-24
TR-36
LxHxD
0.98 x 1.54 x 2.79
25 x 39 x 71
1.18 x 1.65 x 2.91
30 x 42 x 74
1.77 x 1.73 x 3.74
45 x 44 x 95
2.24 x 1.65 x 4.37
57 x 42 x 111
W
0.39
10
0.63
16
0.94
24
1.42
36
A
2.28
58
2.40
61
2.83
72
3.23
82
B
0.57
14.5
0.75
19
0.87
22
0.87
22
C
1.02
26
1.22
31
1.34
34
1.59
40.5