56
SOCOMEC - Ref. : 875 508A
Example:
To reset all values for Diris number 5
to zero, the following frame should be
sent:
Diris Am reply: identical to message
sent
SAVED COMMAND (RESET)
The following command should be
done to save programming parame-
ters changes for Diris number 5.
Nota :
Diris Am will not
reply to this com-
mand.
NB:
To reset several parameters to zero,
add the corresponding figure indica-
ted in the “text” column.
Example: reset Max P+ and kvarh + to
zero: 2 = 100 = 102 (Hex)
Slave
05
Function
06
Address
High-order
04
Address
Low-order
00
Word n°
High-order
10
Word n°
Low-order
00
CRC 16
84BE
Slave
05
Function
06
Address
High-order
06
Address
Low-order
00
Values
0000
CRC 16
88C6
Decimal Hexa.
N° of Text
Unit
address address
words
(Hex.)
1024
400
1
reset to zero for:
0: Max3I
1: MaxP+
2: MaxP-
3: MaxQ+
4: MaxQ-
5: MaxS
6: Hour meter
7: kWh+
8: kvarh+
9: kVA
10: kWh-
11: kvarh-
12: all parameters
/
RESET TO ZERO: ENERGY METERS AND MAX. VALUES (FUNCTION 6):
Zone size: 1 word or 1 hexadecimal