34
SOCOMEC - Ref. : 875 508A
34
SOCOMEC - Réf. : 875 508A
TERMINALS
The Diris Am consists of 1 - 6 mm
2
(flexible wires) and 1.5 - 10 mm
2
(rigid)
connection terminals for current, volta-
SAFETY INSTRUCTIONS (U, I AND F)
To avoid damage to the device plea-
se ensure the following points are
respected before connecting:
• the connections follow the diagram
shown on the rear of the device,
• the indications on the rear face of
the case,
• power supply: 110 to 440 V AC or
NB:
The use of BS 88 2A gG fuses is
recommended for power supply and
voltage input protection.
NB:
The maximum coupling torque for
each screw is 0.4 Nm.
120 to 350 V DC (+/- 10 %),
• 50 or 60 Hz network,
• maximum 700 V AC phase/phase
for input terminals or 404 V AC bet-
ween phases/neutral,
• 6A maximum current (via current
transformer[s]).
CONNECTION
UNBALANCED THREE-PHASE NETWORK (4 LNB)
N
P1
S1
P1
S1
L1 (R)
L2 (S)
L3 (T)
P1
S1
FUSES
110 to 440 V AC
120 to 350 V DC
2 A
S2 S1 S2 S1 S2
S1
I2
I3
I1
V1
V2 V3 VN
AUX
N
P1
S1
P1
S1
L1 (R)
L2 (S)
L3 (T)
P1
S1
110 to 440 V AC
120 to 350 V DC
S2 S1 S2 S1 S2
S1
I2
I3
I1
V1
V2 V3 VN
AUX
A
A
A
a
a
a
DIRIS 272 A GB
DIRIS 273 A GB
The Diris Am is fitted on a DIN rail
onto a panel or on the front of a
control panel with a special mounting
kit. (Please contact us for more infor-
mation)
Recommendations:
• Install the Diris Am at least 30 cm
from a switching device (switch,
contactor, etc.)
• Avoid proximity to systems which
generate electromagnetic interfe-
rence
• Avoid vibrations with accelerations
in excess of 1 G for frequencies
below 60 Hz.
INSTALLATION
CLIMATIC ENVIRONMENT
To guarantee optimal operation, it
is recommended to use this equip-
ment at -10° to 55 °C with relative
humidity between 20 and 95 %.
During operation, the instrument
can tolerate an ambient temperatu-
re of - 15 °C.
ge, auxiliary supply and other options.
Содержание DIRIS Am
Страница 30: ...SOCOMEC R f 875 508 A 31 FRAN AIS...