For 250, 300 & 600 KCMIL (200 , 260 400A) break off all removable 

parts (highlighted on the picture).

For 1/0 & (100A ) do not remove any parts.

Terminal shrouds can 

be locked in place 

using locking points

Print: 90 g/m

2

 - open format 432 x 279 mm - folded 216 x 279 mm with staples - R/V - B&W

The ATyS FT shall be maintained in accordance with industry standards and as per instructions in the ATyS FT 

instruction sheet.

As per NFPA 110 requirements for emergency and standby power systems the ATyS FT should be inspected 

and should be exercised under load at least monthly.

Refer to step 5 for instructions for manual, "non-electric", offload operations for service.

Terminal shrouds 

contain provisions for 

voltage sensing

Push back to 

click in place.

NO. OF POLES

REFERENCE*

100-200A

2P

96982020

3P/2P+N

96983020

4P/3P+N

96984020

260-400A

2P

96982040

3P/2P+N

96983040

4P/3P+N

96984040

* Refs: top and bottom

Top and bottom protection against direct contact with terminals or connecting parts.

Fix the terminal shrouds in place and push back

V

Place the transparent 

plastic piece to cover 

the auxiliary conacts 

and lock in place in 

order to protect from 

direct contacts.

Use the correct protection according to your 

auxiliary contact circuit and your load

Switch has 2 pre-installed auxilliary contacts, 

the kit below is for 2 additional contacts with 

protection against direct contact.

Ref : 96990021

a

b

PH2 screwdriver

Tightening torque

17.7 lb.in / 2 N.m / PH2

Make sure contact 

is correctly activated

AUXILIARY CONTACT ELECTRICAL CHARACTERISTICS
Rated current (125-480 VAC)

22 A

Rated current (125 VDC)

0.5A

Rated current (250 VDC)

0.25 A

Rated horse power up to 250 VAC

½ HP

Rated horse power up to 480 VAC

¼ HP

Recommended wire section for 22A

10 AWG

4 mm²

Terminal tightening torque

7.9 lb.in / 0.9 Nm

1

1

NO NC

COM

2

2

3

3

Installing power terminal shrouds (optional accessories)

PERIODIC MAINTENANCE

6A

Additional auxiliary contacts

6B

WARNING

More than one live circuit.

Disconect all sources of supply before servicing and/or before using the manual operation.

Remove pre-installed auxillary contact

1

Assemble contacts with parts from 

kit as shown below

2

Assemble optional aux contact and  

pre-installed aux contact together

3

4

1

2

3

Содержание ATyS FT

Страница 1: ...s recommended to replace the complete product Installation standards must be respected Accessories Accessories are not included and must be ordered seperatly Terminal shrouds see step 6A Additional aux contacts ref 96990021 Digiware I O 10 ref 48290140 Transformer 480 240 VAC SPARTAN SP350MQMJ Controller 24 VDC aux power supply 6W minimum type SELV mandatory with I 0 10 Modules Power terminal lugs...

Страница 2: ... 10 47 266 30 1 25 31 80 3 85 98 70 1 38 35 20 508 16 406 12 305 2P N 3P 11 85 301 30 1 25 31 80 5 49 133 70 1 38 35 20 508 16 406 12 305 3P N 4P 13 24 336 30 1 25 31 80 6 60 168 70 1 38 35 20 508 16 406 12 305 260 400A 2P 11 67 296 30 1 55 39 30 5 128 60 1 97 50 48 1220 24 610 12 305 2P N 3P 13 63 346 30 1 55 39 30 7 178 60 1 97 50 48 1220 24 610 12 305 3P N 4P 15 60 396 30 1 55 39 30 8 97 228 60...

Страница 3: ...831 Contact us 1 6 250 KCMIL 275 31 1 5 16 70 8 8 5mm 1 25 4 100 200 A CMC LA 300R 39542020 2 1 6 300 KCMIL 275 31 1 5 16 70 8 8 5mm 1 12 28 4 39543020 3 39544020 4 260 400 A CMC LA 630R 39542040 2 1 4 600 KCMIL 550 62 1 1 2 310 35 8mm 1 79 45 7 39543040 3 39544040 4 260 400 A Ilsco D3096 Contact us 1 4 600 KCMIL 600 67 8 1 2 310 35 8mm 1 79 45 7 Power cable connections For 100A use 1 0 AWG For 20...

Страница 4: ...ers not delivered with the product Fix FASTON connectors according to the table in step 2C Max 2 FASTON per pole Wires must not be in contact with active voltage points such as unused FASTON connections and lugs In order to do so any unused or loose cables must be tensed then fixed on a non conductive part of the transfer switch use cable tie fixation points as shown in the images below 1 Pass wir...

Страница 5: ...4 4 5 3 lb in Sensing source 2 SOURCE 2 L1 L2 L3 N Voltage sensing inputs source 2 voltage supply L1 L2 Inputs 71 IN1 SWITCH IN POS1 Do not connect to any external power supply AWG 20 14 0 5 2 5mm 72 IN2 SWITCH IN POS 2 73 IN3 DOOR OPEN 74 IN4 programmable input 4 75 IN5 programmable input 5 76 IN6 programmable input 6 70 Common point for inputs Aux power supply 81 82 negative terminal for aux sup...

Страница 6: ...n the configuration will go as follow SMART WIZARD CONFIG For advanced configuration go to parameters menu Language Source config Time date Switch Application Product Name Communication In STEP 5 8 of the wizard config make sure the network detected matches your network In STEP 6 8 make sure the switch technology parameter is set to ATyS FT If a fault is shown on the controller correct the associa...

Страница 7: ...he LCD screen that may show distortion below 32 F 0 C Inspection of power contacts WARNING More than one live circuit Disconnect all sources of supply before servicing and or before using the manual operation Clip to maintain cover upright Slide cover to access service handle hole For manual operation operate handle 4 up from S2 to S1 down from S1 to S2 FAST OPERATION Recommendation carry out one ...

Страница 8: ...and push back V Place the transparent plastic piece to cover the auxiliary conacts and lock in place in order to protect from direct contacts Use the correct protection according to your auxiliary contact circuit and your load Switch has 2 pre installed auxilliary contacts the kit below is for 2 additional contacts with protection against direct contact Ref 96990021 a b PH2 screwdriver Tightening ...

Отзывы: