RTSE FASTON CONNECTIONS
VOLTAGE TRANSFORMER
480 VAC
240 VAC
PRIMARY
SECONDARY
NETWORK TYPE
TYPE
SOURCE
A
B
C
N
H1
H4
X1
X4
240 VAC
2P
S2
S2A & 201
S2B
None
(1)
None
(1)
S1
S1A & 102
S1B
None
(1)
None
(1)
120/240 VAC
2P + N
S2
S2A & 201
S2B
None
(1)
S2N
S1
S1A & 102
S1B
None
(1)
S1N
208 VAC
3P
S2
S2A & 201
S2B
S2C
None
(1)
S1
S1A & 102
S1B
S1C
None
(1)
120/208 VAC
3P+N / 4P
S2
S2A & 201
S2B
S2C
S2N
S1
S1A & 102
S1B
S1C
S1N
277/480 VAC
3P+N / 4P
S2
S2A
S2B
S2C
S2N & 201
S1
S1A
S1B
S1C
S1N & 102
480 VAC + transfo
3P
S2
2xS2A
2xS2B
S2C
-
T2A
T2B
T2A'
T2B'
S1
2xS1A
2xS1B
S1C
-
T1A
T1B
T1A'
T1B'
(1) Cables which are not used are to be fastened as shown in image 4 of step 2B.
Connect the faston on the switch connexion according to your network and the table below:
Connection of harness on the switch
Controller connection details
2D
2C
TYPE
TERMINAL N° DESCRIPTION
CHARACTERISTICS
RECOMENDED
CROSS SECTION
TIGHTENING
TORQUE
Sensing source 1
SOURCE 1
L1/L2/L3/N
Voltage sensing inputs source 1
& voltage supply (L1-L2)
Sensing voltage
50 - 575 V.a.c P-P - 50/60 Hz (+/- 10%)
Supply voltage (L1-L2)
88 - 576 V.a.c - 50/60Hz (+/- 10%) Ui 600V
AWG 18-14
0.75-2.5mm²
0.5-0.6 Nm
4.4-5.3 lb.in
Sensing source 2
SOURCE 2
L1/L2/L3/N
Voltage sensing inputs source 2
& voltage supply (L1-L2)
Inputs
71
IN1: SWITCH IN POS1
Do not connect to any external power
supply
AWG 20-14
0.5-2.5mm²
72
IN2: SWITCH IN POS 2
73
IN3: DOOR OPEN
74
IN4: programmable input 4
75
IN5: programmable input 5
76
IN6: programmable input 6
70
Common point for inputs
Aux power supply
81/82
- : negative terminal for aux supply
+: positive terminal of aux supply
12-24 Vd.c.
Outputs
12/14/11
OUT1: POS 1 ORDER
Dry contacts
8A / 277 VAC 50/60 Hz
5A / 24 VDC
AWG 16-14
1.5-2.5mm²
22/24/21
OUT2: POS 2 ORDER
32/34/31
OUT3: programmable output 3
42/44/41
OUT4: programmable output 4
52/54/51
OUT5: programmable output 5 (latching)
62/64/61
OUT6: genset start relay
Current transformers
IN/I3/I2/I1
CT neutal / CT phase C / CT phase B / CT phase A
CT input 1A or 5A
Serial connection
RS485
Connection RS485
-: negative terminal of RS485 bus
+: positive terminal of RS485 bus
NC : Ground
RS485 bus insulated
LiYCY shielded twisted pair
30-14 AWG / 0.14 to 1.5 mm²
1.9 - 2.2 Lb.in
0.22 -0.25 Nm
Digiware*
DIGIBUS
Connection point for I/O 10 optional accessories &
digiware connection (must use 24 VDC input)
RJ 45 digiware cable
-
-
* For more information check I/O module instruction sheet ref 545597
Wiring harness connectors to place on controller.
Bottom view
Top view