TYPE
TERMINAL N°
DESCRIPTION
CHARACTERISTICS
RECOMENDED CROSS
SECTION
Switch power input
101-102
Order switch to position S1
194-304 VAC 8 A for at
least 100 ms 50/60 Hz
17-14 AWG
1-2.5 mm²
201-202
Order switch to position S2
Switch Signalization output
333-334
Contact closed if cover is closed
Internal use for
ATyS C66 controller
313-314
Contact closed if the switch is in position S1
323-324
Contact closed if the switch is in Position S2
See step
6B
for Auxiliary
contacts
Connector tightening torque
0.5 N.m / 4.4 Lb.in
Mounting & connecting the cable harness
2A
Mounting the cable harness on the Switch
2B
SOURCE 2
A
A
B
B
C
C
N
N
SOURCE 1
For details on the cable harness wiring diagram and integration see Cable harness Quickstart guide
ref 551401.
Cable harness without transformer (
ref. 96964000
) delivered with
96AX XXXX
products.
Cable harness for connections with transformer (
ref. 96974000
) delivered with
968X XXXX
products.
Note: transformers not delivered with the product.
Fix FASTON connectors
according to the table in
step
2C
.
(Max 2 FASTON per pole).
Wires must not be in contact with active voltage points such as unused
FASTON connections and lugs. In order to do so any unused or loose
cables must be tensed then fixed on a non conductive part of the transfer
switch (use cable tie fixation points as shown in the images below).
1
Pass wiring harness in the integrated
cable duct.
After all the faston cables have
been connected make sure
the cables are tight and fix
them in place using the cable
tie point shown below.
This switch also includes provision
for additional cable ties these can be
used to maintain cables connected to
the auxiliary contacts.
Use the cable tie connection point on the side of the
switch shown above to maintain any unused cables
(for 2P, 2P+N or 3P switches).
3
4
5
After fixing the FASTON
maintain the wires in place
wiring connexion point.
2
CONTROL
POSITION OUTPUTS
101
102
201
202
334 333
314 313 324 323
Connectors
Tightening
Torque:
0.5Nm/4.4lb.in
194-304Vac 50-60Hz (>100ms)
S2
S2
S2
S1
S1
S1
Cover Closed
black cables
for source 2
red cables
for source 1