TYPE

TERMINAL N°

DESCRIPTION

CHARACTERISTICS

RECOMENDED CROSS 

SECTION

Switch power input

101-102

Order switch  to position S1

194-304 VAC 8 A for at 

least 100 ms 50/60 Hz

17-14 AWG

1-2.5 mm²

201-202

Order switch to position S2

Switch Signalization output

333-334

Contact closed if cover is closed

Internal use for 

ATyS C66 controller

313-314

Contact closed if the switch is in position S1

323-324

Contact closed if the switch is in Position S2

See step 

6B

 

for Auxiliary 

contacts 

Connector tightening torque 

0.5 N.m / 4.4 Lb.in

Mounting & connecting the cable harness

2A

Mounting the cable harness on the Switch

2B

SOURCE 2

A

A

B

B

C

C

N

N

SOURCE 1

For details on the cable harness wiring diagram and integration see Cable harness Quickstart guide 

ref 551401.

Cable harness without transformer (

ref. 96964000

) delivered with 

96AX XXXX

 products.

Cable harness for connections with transformer (

ref. 96974000

) delivered with 

968X XXXX

 products.

Note: transformers not delivered with the product.

Fix FASTON connectors 

according to the table in 

step 

2C

.  

(Max 2 FASTON per pole).

Wires must not be in contact with active voltage points such as unused 

FASTON connections and lugs. In order to do so any unused or loose 

cables must be tensed then fixed on a non conductive part of the transfer 

switch (use cable tie fixation points as shown in the images below).

1

Pass wiring harness in the integrated 

cable duct.

After all the faston cables have 

been connected make sure 

the cables are tight and fix 

them in place using the cable 

tie point shown below.

This switch also includes provision 

for additional cable ties these can be 

used to maintain cables connected to 

the auxiliary contacts.

Use the cable tie connection point on the side of the 

switch shown above to maintain any unused cables 

(for 2P, 2P+N or 3P switches).

3

4

5

After fixing the FASTON 

maintain the wires in place 

wiring connexion point.

2

CONTROL

POSITION OUTPUTS

101

102

201

202

334   333

314 313 324 323

Connectors

Tightening

Torque:

0.5Nm/4.4lb.in

194-304Vac  50-60Hz (>100ms)

S2

S2

S2

S1

S1

S1

Cover Closed

black cables 

for source 2

red cables 

for source 1

Содержание ATyS FT

Страница 1: ...s recommended to replace the complete product Installation standards must be respected Accessories Accessories are not included and must be ordered seperatly Terminal shrouds see step 6A Additional aux contacts ref 96990021 Digiware I O 10 ref 48290140 Transformer 480 240 VAC SPARTAN SP350MQMJ Controller 24 VDC aux power supply 6W minimum type SELV mandatory with I 0 10 Modules Power terminal lugs...

Страница 2: ... 10 47 266 30 1 25 31 80 3 85 98 70 1 38 35 20 508 16 406 12 305 2P N 3P 11 85 301 30 1 25 31 80 5 49 133 70 1 38 35 20 508 16 406 12 305 3P N 4P 13 24 336 30 1 25 31 80 6 60 168 70 1 38 35 20 508 16 406 12 305 260 400A 2P 11 67 296 30 1 55 39 30 5 128 60 1 97 50 48 1220 24 610 12 305 2P N 3P 13 63 346 30 1 55 39 30 7 178 60 1 97 50 48 1220 24 610 12 305 3P N 4P 15 60 396 30 1 55 39 30 8 97 228 60...

Страница 3: ...831 Contact us 1 6 250 KCMIL 275 31 1 5 16 70 8 8 5mm 1 25 4 100 200 A CMC LA 300R 39542020 2 1 6 300 KCMIL 275 31 1 5 16 70 8 8 5mm 1 12 28 4 39543020 3 39544020 4 260 400 A CMC LA 630R 39542040 2 1 4 600 KCMIL 550 62 1 1 2 310 35 8mm 1 79 45 7 39543040 3 39544040 4 260 400 A Ilsco D3096 Contact us 1 4 600 KCMIL 600 67 8 1 2 310 35 8mm 1 79 45 7 Power cable connections For 100A use 1 0 AWG For 20...

Страница 4: ...ers not delivered with the product Fix FASTON connectors according to the table in step 2C Max 2 FASTON per pole Wires must not be in contact with active voltage points such as unused FASTON connections and lugs In order to do so any unused or loose cables must be tensed then fixed on a non conductive part of the transfer switch use cable tie fixation points as shown in the images below 1 Pass wir...

Страница 5: ...4 4 5 3 lb in Sensing source 2 SOURCE 2 L1 L2 L3 N Voltage sensing inputs source 2 voltage supply L1 L2 Inputs 71 IN1 SWITCH IN POS1 Do not connect to any external power supply AWG 20 14 0 5 2 5mm 72 IN2 SWITCH IN POS 2 73 IN3 DOOR OPEN 74 IN4 programmable input 4 75 IN5 programmable input 5 76 IN6 programmable input 6 70 Common point for inputs Aux power supply 81 82 negative terminal for aux sup...

Страница 6: ...n the configuration will go as follow SMART WIZARD CONFIG For advanced configuration go to parameters menu Language Source config Time date Switch Application Product Name Communication In STEP 5 8 of the wizard config make sure the network detected matches your network In STEP 6 8 make sure the switch technology parameter is set to ATyS FT If a fault is shown on the controller correct the associa...

Страница 7: ...he LCD screen that may show distortion below 32 F 0 C Inspection of power contacts WARNING More than one live circuit Disconnect all sources of supply before servicing and or before using the manual operation Clip to maintain cover upright Slide cover to access service handle hole For manual operation operate handle 4 up from S2 to S1 down from S1 to S2 FAST OPERATION Recommendation carry out one ...

Страница 8: ...and push back V Place the transparent plastic piece to cover the auxiliary conacts and lock in place in order to protect from direct contacts Use the correct protection according to your auxiliary contact circuit and your load Switch has 2 pre installed auxilliary contacts the kit below is for 2 additional contacts with protection against direct contact Ref 96990021 a b PH2 screwdriver Tightening ...

Отзывы: