ATyS  C66

AUTO

LCD display

Source and 

switch synoptic

Standard code for programming : 1000

Manual operation buttons 

and indicator

Communication 

indicator LED

Switch not in automatic mode 

indicator LED

Automatic button and 

LED indicator

Test button and indicator for 

load tests / no load tests

Short press for lamp test / 

Long press to reset faults

Power, Fault and alarm LED

Navigation buttons

Change dashboard / set screen 

as favorite

3

Controller Interface

When powered for the first time the controller will prompt the user to configure using the wizard.

 

To access the wizard input code 1000 then the configuration will go as follow:

SMART WIZARD CONFIG:

For advanced configuration go to parameters menu.

Language

Source config

Time & date

Switch & 

Application

Product Name

Communication

In STEP 5/8 of the wizard config make sure the network detected matches your network.

In STEP 6/8 make sure the “switch technology” parameter is set to “ATyS DT”.

If a fault is shown on the controller, correct the associated fault and clear by doing a long press (>3s) on the lamp test button.

Left side hinge door

Right side hinge door

Mounting the cable harness on the controller 

2E

or

For details on the controller connectors refer to step 2D, after inserting the required connectors use the cable tie connection points shown below to 

maintain the cables in place:

black cables

red cables

b

b

b

b

b

b

b

b

b

r

r

r

r

r

r

r

Содержание ATyS DT

Страница 1: ...standards must be respected Accessories Accessories are not included and must be ordered seperatly Terminal shrouds see step 6A Additional aux contacts ref 96990021 Digiware I O 10 ref 48290140 Transformer 480 240 VAC SPARTAN SP350MQMJ Controller 24 VDC aux power supply 6W minimum type SELV mandatory with I 0 10 Modules Power terminal lugs see step 1D For further details refer to the product instr...

Страница 2: ...t view Side view Switch top view Controller dimensions 1B SWITCH DIMENSIONS MINIMUM ENCLOSURE SIZE A B L P H W D in mm in mm in mm in mm in mm in mm in mm 100 200A 3P 11 85 301 30 1 25 31 80 5 49 133 70 1 38 35 36 915 16 406 12 305 3P N 4P 13 24 336 30 1 25 31 80 6 60 168 70 1 38 35 36 915 16 406 12 305 260 400A 3P 13 63 346 30 1 55 39 30 7 178 60 1 97 50 60 1524 24 610 12 305 3P N 4P 15 60 396 30...

Страница 3: ...4 100 200 A CMC LA 300R 39542020 2 1 6 300 KCMIL 275 31 1 5 16 70 8 8 5mm 1 12 28 4 39543020 3 39544020 4 260 400 A CMC LA 630R 39542040 2 1 4 600 KCMIL 550 62 1 1 2 310 35 8mm 1 79 45 7 39543040 3 39544040 4 260 400 A Ilsco D3096 Contact us 1 4 600 KCMIL 600 67 8 1 2 310 35 8mm 1 79 45 7 Power cable connections For 100A use 1 0 AWG For 200A use 250 KCMIL For 260A use 300 Kcmil For 400A use 600 Kc...

Страница 4: ...e in step 2C Max 2 FASTON per pole Wires must not be in contact with active voltage points such as unused FASTON connections and lugs In order to do so any unused or loose cables must be tensed then fixed on a non conductive part of the transfer switch use cable tie fixation points as shown in the images below 1 Pass wiring harness in the integrated cable duct After all the faston cables have been...

Страница 5: ...IN I3 I2 I1 CT neutral CT phase C CT phase B CT phase A CT input 1A or 5A Serial connection RS485 Connection RS485 negative terminal of RS485 bus positive terminal of RS485 bus NC Ground RS485 bus insulated LiYCY sheilded twisted pair 30 14 AWG 0 14 to 1 5 mm 1 9 2 2 Lb in 0 22 0 25 Nm Digiware DIGIBUS Connection point for I O 10 optional accessories must use 24 VDC input RJ 45 digiware cable For ...

Страница 6: ...e configuration will go as follow SMART WIZARD CONFIG For advanced configuration go to parameters menu Language Source config Time date Switch Application Product Name Communication In STEP 5 8 of the wizard config make sure the network detected matches your network In STEP 6 8 make sure the switch technology parameter is set to ATyS DT If a fault is shown on the controller correct the associated ...

Страница 7: ...and the bottom switch handle to the bottom position Interlocking mechanism The mechanical interlock ensures that S1 and S2 are mutually exclusive and inhibits one switch from being closed unless the other switch is open Warning when manually switching always place one of the two handles in the OPEN position BEFORE switching the second handle 4 1 2 3 OPERATING VOLTAGE 50 60 10 HZ NETWORK MINIMUM CO...

Страница 8: ... circuit and your load The ATyS DT switch has 4 pre installed auxiliary contacts two of which are reserved for use for harness This kit includes two additional contacts it is therefore recommended to order two sets of this kit for ATyS DT switches Ref 96990021 a b PH2 screwdriver Tightening torque 17 7 lb in 2 N m PH2 Make sure contact is correctly activated AUXILIARY CONTACT ELECTRICAL CHARACTERI...