See step 6B for 

Auxiliary contacts 

Mounting the cable harness on the Switch

2B

SWITCH

TYPE

TERMINAL N°

DESCRIPTION

CHARACTERISTICS

RECOMENDED

 

CROSS SECTION

S1

Switch Power input

1101-1102

Order switch to position S1

194-304 VAC8A for at least 

100ms 50/60Hz

17-14 AWG

1-2.5 mm²

1201-1202

Order switch to OPEN Switch S1

Switch Signalization output

1333-1334

Contact closed if cover of switch S1 is closed

internal use for C66 controller

1313-1314

Contact closed if the switch is in position S1

1323-1324

Contact closed if the switch S1 is OPEN

S2

Switch Power input

2101-2102

Order switch to OPEN S2

194-304 VAC8A for at least 

100ms 50/60Hz

2201-2202

Order switch to position S2

Switch Signalization output

2333-2334

Contact closed if cover of switch S2 is closed

internal use for ATyS C66 

controller

2313-2314

Contact closed if the switch S2 is OPEN

2323-2324

Contact closed if the switch is in position S2

Connector tightening torque 

0.5 N.m / 4.4 Lb.in

SOURCE 2

A

A

B

B

C

C

N

N

SOURCE 1

Fix FASTON connectors 

according to the table in 

step 

2C

.  

(Max 2 FASTON per pole).

Wires must not be in contact with active voltage points such as unused

FASTON connections and lugs. In order to do so any unused or loose

cables must be tensed then fixed on a non conductive part of the transfer

switch (use cable tie fixation points as shown in the images below).

1

Pass wiring harness in the integrated 

cable duct.

After all the faston cables have been 

connected make sure the cables are tight 

and fix them in place using the cable tie 

point shown below.

This switch also includes provision 

for additional cable ties these can be 

used to maintain cables connected to 

the auxiliary contacts.

Use the cable tie connection point on the side of 

the switch shown above to maintain any unused 

cables (for 3P switches).

Mandatory

Optional

3

4

5

After fixing the FASTON 

maintain the wires in place 

wiring connexion point.

2

CONTROL

POSITION OUTPUTS

101

102

201

202

334   333

314 313 324 323

Connectors

Tightening

Torque:

0.5Nm/4.4lb.in

194-304Vac  50-60Hz (>100ms)

S2

S2

S2

S1

S1

S1

Cover Closed

S2

OPEN

S1

OPEN

POSITION        CONNECTION

1A1          2A1

3A1

C             NC

NO

1B1          2B1

C             NC

NO

3B1

1C1          2C1

3C1

1D1          2D1

3D1

Reserved !

Reserved !

For Product Operation

C             NC

NO

C             NC

NO

black cables for source 2

red cables 

for source 1

Содержание ATyS DT

Страница 1: ...standards must be respected Accessories Accessories are not included and must be ordered seperatly Terminal shrouds see step 6A Additional aux contacts ref 96990021 Digiware I O 10 ref 48290140 Transformer 480 240 VAC SPARTAN SP350MQMJ Controller 24 VDC aux power supply 6W minimum type SELV mandatory with I 0 10 Modules Power terminal lugs see step 1D For further details refer to the product instr...

Страница 2: ...t view Side view Switch top view Controller dimensions 1B SWITCH DIMENSIONS MINIMUM ENCLOSURE SIZE A B L P H W D in mm in mm in mm in mm in mm in mm in mm 100 200A 3P 11 85 301 30 1 25 31 80 5 49 133 70 1 38 35 36 915 16 406 12 305 3P N 4P 13 24 336 30 1 25 31 80 6 60 168 70 1 38 35 36 915 16 406 12 305 260 400A 3P 13 63 346 30 1 55 39 30 7 178 60 1 97 50 60 1524 24 610 12 305 3P N 4P 15 60 396 30...

Страница 3: ...4 100 200 A CMC LA 300R 39542020 2 1 6 300 KCMIL 275 31 1 5 16 70 8 8 5mm 1 12 28 4 39543020 3 39544020 4 260 400 A CMC LA 630R 39542040 2 1 4 600 KCMIL 550 62 1 1 2 310 35 8mm 1 79 45 7 39543040 3 39544040 4 260 400 A Ilsco D3096 Contact us 1 4 600 KCMIL 600 67 8 1 2 310 35 8mm 1 79 45 7 Power cable connections For 100A use 1 0 AWG For 200A use 250 KCMIL For 260A use 300 Kcmil For 400A use 600 Kc...

Страница 4: ...e in step 2C Max 2 FASTON per pole Wires must not be in contact with active voltage points such as unused FASTON connections and lugs In order to do so any unused or loose cables must be tensed then fixed on a non conductive part of the transfer switch use cable tie fixation points as shown in the images below 1 Pass wiring harness in the integrated cable duct After all the faston cables have been...

Страница 5: ...IN I3 I2 I1 CT neutral CT phase C CT phase B CT phase A CT input 1A or 5A Serial connection RS485 Connection RS485 negative terminal of RS485 bus positive terminal of RS485 bus NC Ground RS485 bus insulated LiYCY sheilded twisted pair 30 14 AWG 0 14 to 1 5 mm 1 9 2 2 Lb in 0 22 0 25 Nm Digiware DIGIBUS Connection point for I O 10 optional accessories must use 24 VDC input RJ 45 digiware cable For ...

Страница 6: ...e configuration will go as follow SMART WIZARD CONFIG For advanced configuration go to parameters menu Language Source config Time date Switch Application Product Name Communication In STEP 5 8 of the wizard config make sure the network detected matches your network In STEP 6 8 make sure the switch technology parameter is set to ATyS DT If a fault is shown on the controller correct the associated ...

Страница 7: ...and the bottom switch handle to the bottom position Interlocking mechanism The mechanical interlock ensures that S1 and S2 are mutually exclusive and inhibits one switch from being closed unless the other switch is open Warning when manually switching always place one of the two handles in the OPEN position BEFORE switching the second handle 4 1 2 3 OPERATING VOLTAGE 50 60 10 HZ NETWORK MINIMUM CO...

Страница 8: ... circuit and your load The ATyS DT switch has 4 pre installed auxiliary contacts two of which are reserved for use for harness This kit includes two additional contacts it is therefore recommended to order two sets of this kit for ATyS DT switches Ref 96990021 a b PH2 screwdriver Tightening torque 17 7 lb in 2 N m PH2 Make sure contact is correctly activated AUXILIARY CONTACT ELECTRICAL CHARACTERI...

Отзывы: