See step 6B for
Auxiliary contacts
Mounting the cable harness on the Switch
2B
SWITCH
TYPE
TERMINAL N°
DESCRIPTION
CHARACTERISTICS
RECOMENDED
CROSS SECTION
S1
Switch Power input
1101-1102
Order switch to position S1
194-304 VAC8A for at least
100ms 50/60Hz
17-14 AWG
1-2.5 mm²
1201-1202
Order switch to OPEN Switch S1
Switch Signalization output
1333-1334
Contact closed if cover of switch S1 is closed
internal use for C66 controller
1313-1314
Contact closed if the switch is in position S1
1323-1324
Contact closed if the switch S1 is OPEN
S2
Switch Power input
2101-2102
Order switch to OPEN S2
194-304 VAC8A for at least
100ms 50/60Hz
2201-2202
Order switch to position S2
Switch Signalization output
2333-2334
Contact closed if cover of switch S2 is closed
internal use for ATyS C66
controller
2313-2314
Contact closed if the switch S2 is OPEN
2323-2324
Contact closed if the switch is in position S2
Connector tightening torque
0.5 N.m / 4.4 Lb.in
SOURCE 2
A
A
B
B
C
C
N
N
SOURCE 1
Fix FASTON connectors
according to the table in
step
2C
.
(Max 2 FASTON per pole).
Wires must not be in contact with active voltage points such as unused
FASTON connections and lugs. In order to do so any unused or loose
cables must be tensed then fixed on a non conductive part of the transfer
switch (use cable tie fixation points as shown in the images below).
1
Pass wiring harness in the integrated
cable duct.
After all the faston cables have been
connected make sure the cables are tight
and fix them in place using the cable tie
point shown below.
This switch also includes provision
for additional cable ties these can be
used to maintain cables connected to
the auxiliary contacts.
Use the cable tie connection point on the side of
the switch shown above to maintain any unused
cables (for 3P switches).
Mandatory
Optional
3
4
5
After fixing the FASTON
maintain the wires in place
wiring connexion point.
2
CONTROL
POSITION OUTPUTS
101
102
201
202
334 333
314 313 324 323
Connectors
Tightening
Torque:
0.5Nm/4.4lb.in
194-304Vac 50-60Hz (>100ms)
S2
S2
S2
S1
S1
S1
Cover Closed
S2
OPEN
S1
OPEN
POSITION CONNECTION
1A1 2A1
3A1
C NC
NO
1B1 2B1
C NC
NO
3B1
1C1 2C1
3C1
1D1 2D1
3D1
Reserved !
Reserved !
For Product Operation
C NC
NO
C NC
NO
black cables for source 2
red cables
for source 1