Screw Tightening torque
PH1 / 0.2 Nm 1.77 lb.in
Clip the
mounting feet in
the designated
slot
Screws not delivered with product
5.9
+/-0.4
150
+/-1
6.77 - 7 172 - 178
0.25
6,4
R 0.24
R 6,25
0.12
3
1.53
±
0,01
39
±
0,3
0.86
22,05
0.05
±
0,02
15,5
±
0,5
135
°
0.07
2
0.31
±0,004
8
±0,1
Mount the load terminal lugs on the
switch terminals before mounting source
2 terminal lugs.
Backplate mounting
Mounting & connecting controller
1C
Installing terminal lugs (optional accessory)
1D
Use terminal screws and washers supplied with the ATSE
Product
Rating (A)
Designation
Ref. lugs
Quantity
per
reference
Openings
per lug
Size / Section
(AWG)
Pressure screw
torque
Bolt torque
Y
min.
max.
lb.in
Nm
Size in lb.in
Nm
Size
in
mm
100A
Ilsco D0957
Contact us
1
14
1/0
50
5,65
8
70.8 8
5 mm
0.625
15,9
200A
Ilsco D2831
Contact us
1
6
250 KCMIL
275
31,1
5/16 70.8 8
5 mm
1
25,4
100-200 A
CMC LA-300R
39542020
2
1
6
300 KCMIL
275
31,1
5/16 70.8 8
5 mm
1.12
28,4
39543020
3
39544020
4
260-400 A
CMC LA-630R
39542040
2
1
4
600 KCMIL
550
62,1
1/2
310
35
8 mm
1.79
45,7
39543040
3
39544040
4
260-400 A
Ilsco D3096
Contact us
1
4
600 KCMIL
600
67,8
1/2
310
35
8 mm
1.79
45,7
Power cable connections : For 100A use 1/0 AWG / For 200A use 250 KCMIL / For 260A use 300 Kcmil / For 400A use 600 Kcmil copper cables.
Mounting & connecting the cable harness
2A
PE
Insert the 4 door mounting
screws in the designated slot and
push back to clip in lock in place.
For use on a flat surface of
Types 1, 3R, 12 and/ or 12K
enclosure
1
2
Gasket for Type 3R/12
8.66
+/-0.4
220
+/-1
6.30
+/-0.4
160
+/-1
For details on the cable harness wiring diagram and integration see Cable harness Quickstart guide ref 551401.
Cable harness without transformer (ref.
98964000
) delivered with
98AX XXXX
products.
Cable harness for connections with transformer (ref.
98974000
) delivered with
988X XXXX
products.
Note: transformers not delivered with the product.
Door mounting
PE