Programming
Controller ATyS
OPERATION
47
SOCOMEC - Réf. : 532 929 B
PARAMETERS CHARACTERISTICS
Network
nominal
frequency
Network nominal frequency
50 Hz or 60 Hz
50 Hz
1
2
>
Menu Setup
LCD
Denomination
Definition
Setting Default
range
values
1
2
Network
nominal voltage
Phase-Neutral voltage or Phase-Phase voltage
From 100 V to
440 V
220 V
Manual
retransfer
“impulse” or
“contactor”
logic
Outputs control logic: impulse (IMP) or contactor (Con)
Activation of the feature
YES or nO
nO
Imp or con
IMP
Restricted
access code
modification
Restricted access (counters rS1 and rS2) code modification
From 0000 to
9999
5000
Number of
auxiliary contact
Depends on changeover technology
(switch, contactor, breaker)
0 or 2
2
1
2
1
2
1
2
Genset start
signal state
Normally opened or closed. The same state for the 2
sources.
nO or nC
nO
1
2
1
2
Return to 0
position
Allows to go to position 0 in case of network loss
(contactor logic type)
YES or nO
nO
1
2
Number of
permutation
counter Reset
Automatic sequences counter reset
YES or nO
nO
1
2
Programming
code
Programming code modification
From 0000 to
9999
1000
1
2
1
2