Controller ATyS
CONNECTIONS
41
SOCOMEC - Réf. : 532 929 B
Control circuits
Denomination Terminals Description
Characteristics
Recommended
section
Power supply
L3 (104) Phase 3
440 V ac (phase-phase)
1.5 mm
2
Source
L1 (106) Phase 1
maximum, 50 / 60 Hz
Power supply
L1 (203) Phase 1
440 V ac (phase-phase)
1.5 mm
2
Source
L3 (205) Phase 3
maximum, 50 / 60 Hz
Power supply DC
DC-
Power supply 0 V
From 9 V dc to 30 V dc
1.5 mm
2
12Vdc, 24Vdc
DC+
Power V dc
maxi.
Genset
13
Genset
start / stop relay - 2 stable positions
Dry contact
1.5 mm
2
start signal
(1)
14
Programmable state - factory setting = NO, close to start 5A AC1 / 250 V
Control
23
Impulse mode: order to close source
5 A AC1 / 250 V
(impulse,
24
Contactor mode: order to close contactor source
contactor
Breaker mode: order to close breaker source
and breaker
33
Impulse mode: order to close source
5 A AC1 / 250 V
1.5 mm
2
mode to
34
Contactor mode: order to close contactor source
programm)
Breaker mode: order to open breaker source
43
Impulse mode: order to close position 0
5 A AC1 / 250 V
1.5 mm
2
44
Contactor mode: programmable relay O1
Breaker mode: order to close breaker source
Genset
53
Genset
start / stop relay - 2 stable positions
5 A AC1 / 250 V
1.5 mm
2
start signal
(1)
54
Programmable state - factory setting = NO, close to start
Information
301
Auxiliary contact information position 1 CA1
Do not connect to
1.5 mm
2
auxiliary
302
Programmable input 3
any power supply
contacts
303
Auxiliary contact information position 2 CA2
Programmable
304
Programmable input 1
Do not connect to
1.5 mm
2
Inputs
305
Programmable input 2
any power supply
Common
316
Specifique voltage supply
Do not connect to
1.5 mm
2
input
Common terminals 301 to 310
any power supply
(1) Refer to programming, Setup, to modify relay state.
2
2
2
1
2
2
1
1
1
1
1
2
1