Operation
Controller
ATyS
OPERATION
ATyS C40
56
SOCOMEC - Réf. : 532 929 B
Presentation
Operational modes
Programming
Operation
Visualisation
Automatic sequences
PRESENTATION
Enter operation mode:
•
Step 1:
press and hold
the “TEST” push button for 5 s
•
Step 2:
enter the operation code (CE) using
navigation push buttons (code 4000)
•
Step 3:
press “validation”
push button
Exit operation mode:
Press and hold the “TEST” push button for 5 s
or automatic exit without action during around
2 min
Navigate in operation mode:
• Press “TEST” push button to access
different features
• Press “validation” push button to activate
required function
This mode allows in manual mode (not padlocked) to start
a test off load. In automatic mode, it allows to start a test,
on or off load.