![socomec ATyS A15 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/socomec/atys-a15/atys-a15_instruction-manual_1311220008.webp)
8
EN
ATyS Controller A15 - 549779A - SOCOMEC
5. QUICK START
1
2
31
23
13
31
43
15
31
63
17
63
A6
4A
24
14
04
13
-+
-
--
-
-
64A
63A
51
54
52
F1
73
72
F2
71
70
14
15
16
17
103
102
101
302
301
202
201
104
105
106
203
204
205
206
L1
L2
L3
N
L1
L2
L3
N
318-520 ph-ph
184-300 ph-n
318-520 ph-p
h
184-300 ph-n
+-
0I
II
C
Ctrl
OFF
I I
I I
I
I
0
0
C
C
I I
81
82
I0
C
Aux supply
SOURCE
1
S1 IN
S2 IN
DPS OU
T
All fuses 4A type gG
*
*Using a Socomec cable harness kit excludes the need for fuses
SOURCE
2
301 302
5
93
96
X2
Voltage
Sensing
Frequency
Overvoltage Cat.
Mesurement Cat.
50-300V
ac L/N
90-520V
ac L/L
’
50-60Hz
50-60Hz
50-60Hz
IEC 60947-6-1
IEC 61010-2-201
IEC 61010-2-030
III
III
CA
T III
U imp
4kV
Test level ; Between SOURCES
When type tested with IEC 60947-6-1 R
TSE
50Hz
GB/T 14048.1
1
appendix
C
III
6kV
Sour
ce available
Start FT
+ΔU/ΔF
[Hyst]
[Hyst]
-ΔU/ΔF
V
n 230 V a c L/N
Un 400 V a c L/
L
Fn 50Hz
Start
RT
Start FT
Start
RT
T
1
2
3
4
5
6
7
8
9
10
11
12
1,5
- 3
13
8
(0
/+
1)
93
(0/+0,8)
EN
HMI
EN
Connection with A
TyS
EN
Connectors
EN
Hyster
esis & Timers
EN
Technical characteristics
1.
Sour
ce 1 availability information (Gr
een fixed when sour
ce 1 is pr
esent and available
and within thr
eshold limits, gr
een blinking when sour
ce 1 is pr
esent but outside of
thr
eshold limits, of
f when under 50V
AC)
2.
Switch 1 LED position indication (Gr
een fixed when in position 1)
3.
Zer
o position LED indication (Y
ellow when in position 0)
4.
Load
supplied
information
(Gr
een
fixed
when
load
is
supplied
by
an
available
sour
ce)
5.
Switch 2 LED position indications (Gr
een fixed when in position 2)
6.
Sour
ce 2 availability information (Gr
een fixed when sour
ce 2 is pr
esent and available
and within thr
eshold limits, gr
een blinking when sour
ce 2 is pr
esent but outside of
thr
eshold limits, of
f when under 50V
AC)
7.
Auto LED indication (Gr
een fixed when in automatic, blinking when transfer is
ongoing, of
f when in manual mode)
8.
Test LED (Y
ellow fixed when test on load is ongoing)
9.
Configurations dip switches (see settings)
10.
Run LED (Gr
een when pr
oduct is power
ed)
11.
Fault
LED
(Red
blinking
–
long
blink
when
fault
or
inhibit
is
activated
(63A/64A
open),
short blink when a dip switch parameter has been changed and ne
eds validation)
12.
Fir
e (Red when fir
e input is activated)
EN
Dimensions
EN
Settings
EN
Mounting
After changing DIP switch settings pr
ess
RES button shortly (<3s) to validate.
dimensions in mm.
dimensions in mm.
DIP Switch
1.
Network
A
Thr
ee phase network
B
Single phase network
2. Prio
Set
A
Prioritty sour
ce 1
B
No priority
3. Or
der
Mod
A
Contr
ol mode impulse logic
B
Contr
ol mode contactor logic
4. ΔU/ΔF
A
Overvoltage setting at 10% of nom voltage / overfr
equency setting
5% of nominal fr
equency (hyster
esis value is 20% of ΔU/ΔF)
B
Overvoltage setting at 20% of nom voltage / overfr
equency setting
10% of nominal fr
equency (hyster
esis value is 20% of ΔU/ΔF)
5. 0DT
A
Load supply down time of 2 second (0DT = 02 sec)
B
Load supply down time of 0 second (0DT = 0 sec)
6. FT
A
W
ait time of 3s befor
e sour
ce is lost ( Fail timer = 3s)
B
W
ait time of 10s befor
e sour
ce is lost ( Fail timer = 10s)
7/8. R
T
AA
W
ait time of 0min (3s) befor
e sour
ce r
etur
ns ( r
etrun timer = 0min (3s))
AB
W
ait time of 3min befor
e sour
ce r
etur
ns ( r
etrun timer = 3min)
BA
W
ait time of 10min befor
e sour
ce r
etur
ns ( r
etrun timer = 10min)
BB
W
ait time of 30min befor
e sour
ce is lost r
etur
ns ( r
etrun timer = 30min)
Connectors top view
Connectors bottom view
Denomination
Terminal
Description
Characteristics
Contr
ol
signal outputs
(or
ders to
R
TSE)
14
Position II or
der
AC1 – General use – Ie: 5A , Ue: 250 V
.a.c
DC1 – General use – Ie: 5A , Ue: 30 V
.d.c
AC15 - Ie: 3A, Ue: 120 V
.a.c
AC15 - Ie: 1.5A, Ue: 240 V
.a.c
DC13 - Ie: 0.22A, Ue: 125 V
.d.c
DC13 - le: 0.11A, Ue: 250 V
.d.c
15
Position I or
der
16
Position 0 or
der
17
Common point for position
output
RS485
35
NC – Not connected
RS485 Isolated bus
36
Negative electr
ode
37
Positive electr
ode
Genset output
51
Common point
52
Closed to start the Genset
(closed when contr
oller is
power
ed of
f)
AC1 – General use – Ie: 3A , Ue: 250 V
.a.c
DC1 – General use – Ie: 3A , Ue: 30 V
.d.c
AC15 - Ie 54/51: 3A 52/51: 1.5A Ue: 120 V
.a.c
AC15 - Ie 54/51: 1.5A 52/51: 0.75A Ue: 240 V
.a.c
DC13 - Ie 54/51: 0.22A 52/51: 0.22 A 125 V
.d.c
DC13 - Ie 54/51: 0.11A 52/51: 0.11 A 250 V
.d.c
54
Open to start the genset
Contr
oller
inhibit input
63A
Contr
oller is inhibited when this
contact is open
Do not use exter
nal voltage - Power fr
om
common point
64A
Retur
n of
information
from R
TSE
(Position
inputs)
70
Common point for position
inputs
Do not use exter
nal voltage - Power fr
om
common point
71
Position I R
TSE
72
Position II R
TSE
73
Position 0 R
TSE
Fir
e input
F1
Negative electr
ode of the 24 V
.d.c
12-24 V
.d.c
F2
Positive electr
ode of the 24 V
.d.c
Optional
Aux supply
24V
.d.c
81
Negative electr
ode of the 24 V
.d.c
10-30 V
.d.c (Auxiliary supply for contr
oller
,
does not supply R
TSE)
82
Positive electr
ode of the 24 V
.d.c
Sour
ce 1 and
2 voltage
inputs
103
Sour
ce 1 N
Sensing range:
90-520 V
.a.c (ph-ph)
50-300 V
.a.c (ph-n)
45-65 Hz
Supply:
184-300 V
.a.c* (ph-n)
45-65 Hz
Max consumption 10 W
*200-300 V
.a.c in maintained mode
104
Sour
ce 1 L1
105
Sour
ce 1 L2
106
Sour
ce 1 L3
203
Sour
ce 2 N
204
Sour
ce 2 L1
205
Sour
ce 2 L2
206
Sour
ce 2 L3
DPS output
(R
TSE power
supply)
301
Phase output
AC – General use – Ie: 6A , Ue: 250 V
.a.c
DC – General use – Ie: 6A , Ue: 30 V
.d.c
AC15 - Ie: 3A, Ue: 120 V
.a.c
AC15 - Ie: 1.5A, Ue: 240 V
.a.c
DC13 - Ie: 0.22A, Ue: 125 V
.d.c
DC13 - le: 0.11A ,Ue: 250 V
.d.c
302
Neutral output
W
ar
ning : Pr
oduct must be in manual
mode (LED 7 OFF) for configuration
changes.
Standards
DIN rail mounting
1. Mounting
2. Unmounting
Door mounting (IP 40)
IEC 60715
DIN rail