ATyS Controller A15 - 549779A - SOCOMEC
6.2. CONTROLLER HMI
1
2
3
5
4
6
8
9
12
10
7
11
1.
Source 1 availability information (Green fixed when source 1 is present and available within threshold limits, green blinking
when source 1 is present but outside of threshold limits, off when under 50VAC).
2. Switch 1 LED position indication (Green fixed when in position 1).
3. Zero position LED indication (Yellow when in position 0).
4. Load supplied information (Green fixed when load is supplied by an available source)
5.
Switch 2 LED position indications (Green fixed when in position 2).
6. Source 2 availability information (Green fixed when source 2 is present and available within threshold limits, green blinking
when source 2 is present but outside of threshold limits, off when under 50VAC).
7. Auto LED indication (Green fixed when in automatic, blinking when a transfer is ongoing, off when in manual mode or inhi
-
bited or fault is ongoing).
8. Test LED (Yellow fixed when test on load is ongoing).
9. Configurations dip switches (8 dip switches with 2 positions A and B see chapter X.X page X for configuration details).
10. Run LED (Green when product is powered).
11.
Fault LED (Red blinking – long blink when fault or product in inhibited, fast blink when a dip switch parameter has been
changed and needs validation).
12. Fire (Red when fire input is activated).
See Annex I page 29 for more details on the LED indicators