13.2.1.
Manual switching
Use the handle situated on the front panel under the cover
to manoeuvre the changeover switch. To simplify the
operation, it is advised to also use the handle extension
that is delivered with the product.
Check the changeover switch position on the indicator
situated on the front panel before making any operation.
• From position I, turn anti-clockwise to get to
position 0
• From position 0, turn anti-clockwise to get to
position II
• From position II, turn clockwise to get to position 0
• From position 0, turn clockwise to get to position I
(Max 8 nm)
Extension
do not force the product (Max 8 nm).
13.3.
Padlocking
Enables locking in the 0 position (factory coniguration) or in positions I, 0 or II (user conigurable).
It is necessary to conigure padlocking to all positions before installation as access to coniguration is at the back of
the product. Refer to section «8.1. Changing the padlocking coniguration», page 19
Locking is only possible in manual mode (cover open).
Pull on the locking handle to enable the interlock. Lock
by inserting a padlock into the oriice provided for this
purpose.
4 mm min
3/16” min
8 mm min
5/16” min
13.4.
Commissioning / Putting into service
Whilst in manual mode check the wiring and installation. If ok power up the product.
This product must always be put into service by qualified and approved personal.
13.5.
Automatic (remote) mode
Close the cover to enter automatic mode. Make sure that the changeover switch is in automatic mode (AUT LED lit).
13.5.1.
Sealable Auto/Manual cover
Auto/Manu mode can be protected by sealing the standard Auto/Manu cover as shown.