9
EN
ATyS d M - 542 929 C - SOCOMEC
2.2.1. Selection guide
Six ratings 40 / 63 / 80 / 100 / 125 / 160 A
ATyS
d
M
ATyS
t
M
ATyS
g
M
ATyS
p
M
AppLICATIONS
Normal / Backup without automatic controller
•
Normal / Backup with built-in automatic controller
•
•
•
Stable positions
•
•
•
•
Load changeover
•
FUNCTIONS
poWer Supply
External
•
Integrated
•
•
•
operation
Backup manual operation of the 3 positions
•
•
•
•
Electrical (dry contact) control of positions I, 0
and II
•
•*
Automatic control of positions I, 0 and II
•
•
•
Return to 0 position feature upon loss of source
•
Monitoring
3 voltages on networks I and II
•
•
•
Frequency on networks I and II
•
•
•
Phase rotation on networks I and II
•
Asymmetry of networks I and II
•
autoMatic controller configura-
tion
By potentiometer and micro-switch
•
•
By keyboard
•
V
n
, F
n
, V threshold, F threshold
•
•
•
Driving with or without priority
•
•
•
Adjustable operating timers
•
•
•
Control type (impulse or switch / contactor)
•
diSplay
Position, fully visualised breaking
•
•
•
•
LED: source status, automatic mode, fault LED
•
•
•
LED: switch positions, supply, tests, control
•
V, F, timers, number of operations, last event
•
reMote control
Outputs
Generator start / stop order
•
•
Product availability
(not fault and not manual mode)
•
•*
Source available
•
•*
Programmable output (source, availability, fault)
•*
Inputs
Test on load
•
•*
Retransfer
•
•*
Automatic mode inhibit
•
•
•*
Position O order
•
•*
Priority
•
•
•
Other programmable inputs
(test off-load, position control, etc.)
•*
Remote control
Human / Machine Interface (
D10
and
D20
)
•
RS485 communication (MODBUS)
•**
* 3 inputs / 3 outputs (programmable).
** Product reference is different: communication by RS485 connection (MODBUS) allows up to 31 ATyS M to be connected to a PC or a PLC over 1500 m.