Battery installation
The batteries are fitted inside the backbox and connected up in the manner shown, however the final connection to power up the
panel is made during system commissioning, which is done by the servicing organisation.
To fit the batteries inside the panel enclosure:
a
Open out the two tabs on the electronic module at positions
j
and lift open the 'LCD assembly' to an angle 45
o
maximum
k
,
use a non conductive prop
l
, such as a plastic pen, to keep the 'LCD assembly' open.
b
Connect the batteries in the manner illustrated
m
ensuring one of the + connection is left disconnected. Then fit the batteries
inside the enclosure as illustrated
n
.
c
Fit the connector of the battery lead
o
to socket P7 on the Power supply unit.
d
Remove the prop and close the LCD assembly.
Installation instructions
24
12V 7Ah 12V 7Ah
+
-
+
-
P7
BATT
DO NOT open more
than 45 maximum.
o
DO NOT make the final battery
connection. The panel is powered
up during the commissioning stage.
Place a non conductive
prop, such as a plastic pen.
Backbox
LCD assembly
WARNING
Removal of
cover exposes
live parts
DANGER
WARNING
Removal of
cover exposes
live parts
DANGER
Red
Black