Controls at
Access level 2
(Customer mode)
As for controls at Access level 1
plus controls for:
¨
Cancel buzzer
¨
Emergency controls
¨
Clock set
¨
Day/Night mode
¨
Enablement/Disablement
¨
Weekly test
¨
Zone test mode
¨
Display test
¨
Loop status/repair
¨
Firmware version
¨
Site data
Controls at
Access level 3
(Engineer mode)
As for controls at Access level 2
plus controls for:
¨
Delay settings
¨
Calendar settings
¨
External inputs
¨
Serial ports
¨
Weekly test settings
¨
Zone label and linkage
¨
Device settings
¨
Interface channel settings
¨
Sound Signal settings
¨
Zone Cause and Effect
¨
Sound alarm mode & operation
¨
Signal settings
¨
Loop status and map
¨
Site data backup & restore
Controls at
Access level 4
(Maintenance
mode)
As for controls at Access level 3
plus controls for:
¨
Clear logs
¨
Maintenance reminder
¨
Firmware upgrade
¨
Device time averages
¨
Device condition codes
¨
Diagnostics
¨
Reset codes, configuration and
labels to factory default settings
¨
Backup & restore changes
¨
Fast find
¨
Loop power up/down
¨
Start detection
¨
Commissioning mode
¨
Beam alignment
¨
Proprietary Logo
&
Always use the recommended
replacement or equivalent type battery, as there is a
risk of an explosion if incorrect battery is used.
Power supply
Standard
Designed to EN54-4 : 1997
Mains supply
voltage and fuses
230V 50Hz protected by:
FS3 Fuse - 3.15A (T) 250V
Ceramic 20mm x 5mm,
located on PSU.
Input current - 0.45A
Nominal supply
voltage for master
alarm circuits
24V +/- 4V
Lithium Battery
BATT3 on MCB. Type
Panasonic CR2032 3V cell.
CAUTION: Replacement
battery must be the same
or equivalent type battery.
Dispose of used batteries
according to the
manufacturer’s
instructions.
Battery circuit
'BAT1' and fuse
FS1 Fuse 3.15A (T) TE5 on
PSU
PSU volts & fuses
43V (quiescent)
24V
FS6 Fuse 1.0A (T) TE5 on PSU
FS4 Fuse 1.0A TE5 on PSU
Battery
Powersonic PS-1270 F1
2- 12V 7Ah sealed lead acid
batteries that will provide
24 hours standby and
30 minutes alarms,
determined by system loading
via battery standby calculator.
Storage
temperature
-10 to 55ºC
Operating
temperature
-5ºC to 40ºC
Relative Humidity
(Non condensing)
up to 93%
(Temperature 5 to 45°C)
Maximum current
from battery
without mains
connected
1.5A
EN54 Part 4 data
I max a 1.5 A
I max b 1.4 A
I min
UVLO
Ri max
300 mA
20.7 V
±
400mV
1.5
W
&
After power down hazardous voltages
may still be present even if indications are
extinguished.