FIGURE 1.  CSD-1 GAS CONTROL DIAGRAM

CSD-1 required components are factory installed and are shown 

in Figure 2. The Safety High Limit Manual Reset, White-Rodgers 

11B55-104  (P.N.  98054-1)  is  factory  set  for  installation  as  a 

Hydronic Heating Boiler, with maximum stop setting of 250 

°F. 

For installation as a Hot Water Supply Boiler, the stop must be 

reset to a maximum of 210 

°F.

For additional information on this Hot Water Boiler installation, 

see Instruction Manual 321078-000.

The wiring changes brought about by the addition of the Figure 

manual reset High Limit, and the Flow Switch are reflected on 

the wiring diagrams shown in Figure 3.
Boilers  are  shipped  with  a  50  lb.  Relief  Valve  installed  for 

installation as a Hot-Water Heating Boiler. For installation as a 

Hot-Water Supply Boiler the Relief Valve must be replaced. See 

Instruction Manual 321078-000 for further information on relief 

valve for Hot-Water Supply systems.

FIGURE 2.  CSD-1 OUTLET MANIFOLD

GAS CONTROL DIAGRAM

Содержание HW 420

Страница 1: ...rity having jurisdiction requires that the installation must conform to the standard for Controls and Safety Devices for Automatically Fired Boilers ASME CSD 1 The rules of the code cover the requirem...

Страница 2: ...TROL DIAGRAM 3 WIRING DIAGRAM 4 OPERATING SEQUENCE 5 OPERATING SEQUENCE WHEN WIRED AS SHOWN 5 TESTING AND MAINTENANCE 6 INSTRUCTIONS FOR TESTING AND MAINTENANCE 7 DAILY CHECKS 7 WEEKLY CHECKS 7 MONTHL...

Страница 3: ...information on this Hot Water Boiler installation see Instruction Manual 321078 000 The wiring changes brought about by the addition of the Figure 2 manual reset High Limit and the Flow Switch are ref...

Страница 4: ...4 Figure 3 WIRING DIAGRAM WIRING DIAGRAM...

Страница 5: ...the pump providing sufficient water flow the flow switch will close contacts allowing power to be supplied to the transformer through the manual reset high limit 4 Power continues through the normally...

Страница 6: ...nd safety devices operating as intended at all times a periodic testing and maintenance schedule should be set up and followed with results being logged on a regular basis Operators or maintenance tec...

Страница 7: ...bly inspected on a daily basis for normal operation These items should be noted and the differential temperatures recorded during operation If the temperature differential increases by five 5 degrees...

Страница 8: ...8 25589 Highway 1 McBee SC 29101 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Отзывы: