EtherNet/IP Driver Manual
Page 8 of 42
5
CONFIGURING THE FIELDSERVER AS AN ETHERNET/IP CLIENT
For detailed information on FieldServer configuration, refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration
files included with the FieldServer.
This section documents and describes the parameters necessary for configuring the FieldServer to
communicate with an EtherNet/IP Server.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to
enable the FieldServer for EtherNet/IP communications, the driver independent FieldServer buffers need
to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the
“Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side
Map Descriptors” section. Details on how to do this can be found below.
NOTE: In the tables below, * indicates an optional parameter and bold legal values are defaults.
5.1
Client Side Connection Parameters
Section Title
Adapter
Column Title
Function
Legal Values
Adapter
Adapter Name
N1, N2
1
Protocol
Specify protocol used.
EtherNet/IP
UDP_Local_IO_Port
Specify if it is required to receive implicit
IO messages on the non-default port.
1-65534,
2222
Example
// Client Side Connections
Adapters
Adapter
, Protocol
, UDP_Local_IO_Port
N1
, EtherNet/IP
, 2222
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports
available on specific hardware.