Riello ProtoNode Start-up Guide
Page 3 of 43
Quick Start Guide
1. Record the information about the unit. (
Section
2.
Set the device’s COM settings and Node-ID for each of the devices that are to connect to ProtoNode
FPC-N38 or FPC-N39. (
Section
3. FPC-N38: Select the Field Protocol on the S Bank Dip Switches. (
Section
4.
Enable the ProtoNode “Auto Discovery” mode on Dip Switch Bank S. (
Section
5. BACnet MS/TP (FPC-N38): Set the MAC Address on DIP Switch Bank A. (
Section
6. BACnet MS/TP (FPC-N38): Set the BAUD rate of the BACnet MS/TP Field Protocol on DIP Switch
Bank B. (
Section
7.
Connect ProtoNode’s 6 pin RS-485 connector to the RS-485 network that is connected to each of the
devices. (
8.
Connect ProtoNode FPC-N38
’s
3 pin RS-485 port to the Field Protocol cabling, (
Section
or connect ProtoNode FPC-N39
’s
2 pin LonWorks port to the Field Protocol cabling. (
9.
Connect Power to ProtoNode’s 6 pin connector. (
Section
10. When power is applied it will take about 3 minutes for all the devices to be discovered, and the
configuration file to be built. Once Auto-Discovery is complete turn OFF the S3 DIP Switch to save
the configuration settings. (
Section
11. BACnet/IP or Modbus TCP/IP (FPC-N38):
Use the ProtoNode’s embedded tool which is accessed
with a browser, referred to in this manual as the Web Configurator, to change the IP Address. No
changes to the configuration file are necessary. (
Section
12. LonWorks (FPC-N39): The ProtoNode must be commissioned on the LonWorks Network. This needs
to be done by the LonWorks administrator using a LonWorks Commissioning tool. (
Section