Riello ProtoNode Start-up Guide
Page 36 of 43
Appendix B. Vendor Information - Riello
NOTE:
All Modbus TCP/IP registers are the same as the Modbus RTU registers for the serial device. If
this point list is needed, contact the OEM. The Modbus TCP/IP node address of the device is also
the same as the Modbus RTU node address.
Appendix B.1. 905 Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks
Point Name
BACnet
Object Type
BACnet
Object
ID
N2
Data
Type
N2
Address
LonWorks Name
LonWorks SNVT
Reset Curve Boiler Design
AV
1
AO
1
nvi/nvoResCvBlDs_XXX
SNVT_temp_p
Reset Curve Boiler Mild Weather
AV
2
AO
2
nvi/nvoResCvBMWt_XXX
SNVT_temp_p
Reset Curve Outdoor Mild Weather
AV
3
AO
3
nvi/nvoResCvOMWt_XXX
SNVT_temp_p
Reset Curve Outdoor Design
AV
4
AO
4
nvi/nvoResCvOtDs_XXX
SNVT_temp_p
Warm Weather Shutdown
AV
5
AO
5
nvi/nvoWmWthShDn_XXX
SNVT_temp_p
Reset Curve Boiler Maximum
AV
6
AO
6
nvi/nvoResCvBlMx_XXX
SNVT_temp_p
Reset Curve Boiler Minimum
AV
7
AO
7
nvi/nvoResCvBlMn_XXX
SNVT_temp_p
Night Setback
AV
8
AO
8
nvi/nvoNtStbk_XXX
SNVT_temp_p
Power Level For Entire System
AI
9
AI
9
nvoPwrLvl_XXX
SNVT_lev_percent
Cascade Ch Mode X SP
AV
10
AO
10
nvi/nvoCscChMdSP_XXX
SNVT_temp_p
System Supply SP
AI
11
AI
11
nvoSysSupSP_XXX
SNVT_temp_p
System Supply Sensor Temp
AI
12
AI
12
nvoSysSpSnTp_XXX
SNVT_temp_p
Outdoor Sensor Temp
AI
13
AI
13
nvoOutSenTmp_XXX
SNVT_temp_p
Cascade Pump Status
BI
14
DI
14
nvoCscPmpSt_XXX
SNVT_switch
Boiler 1 Available / Present
BI
15
DI
15
nvoB1Avail_XXX
SNVT_switch
Boiler 2 Available / Present
BI
16
DI
16
nvoB2Avail_XXX
SNVT_switch
Boiler 3 Available / Present
BI
17
DI
17
nvoB3Avail_XXX
SNVT_switch
Boiler 4 Available / Present
BI
18
DI
18
nvoB4Avail_XXX
SNVT_switch
Boiler 5 Available / Present
BI
19
DI
19
nvoB5Avail_XXX
SNVT_switch
Boiler 6 Available / Present
BI
20
DI
20
nvoB6Avail_XXX
SNVT_switch
Boiler 7 Available / Present
BI
21
DI
21
nvoB7Avail_XXX
SNVT_switch
Boiler 8 Available / Present
BI
22
DI
22
nvoB8Avail_XXX
SNVT_switch
Boiler 1 Is Active / Heating
BI
23
DI
23
nvoB1ActHt_XXX
SNVT_switch
Boiler 2 Is Active / Heating
BI
24
DI
24
nvoB2ActHt_XXX
SNVT_switch
Boiler 3 Is Active / Heating
BI
25
DI
25
nvoB3ActHt_XXX
SNVT_switch
Boiler 4 Is Active / Heating
BI
26
DI
26
nvoB4ActHt_XXX
SNVT_switch
Boiler 5 Is Active / Heating
BI
27
DI
27
nvoB5ActHt_XXX
SNVT_switch
Boiler 6 Is Active / Heating
BI
28
DI
28
nvoB6ActHt_XXX
SNVT_switch
Boiler 7 Is Active / Heating
BI
29
DI
29
nvoB7ActHt_XXX
SNVT_switch
Boiler 8 Is Active / Heating
BI
30
DI
30
nvoB8ActHt_XXX
SNVT_switch
Boiler 1 Has Error
BI
31
DI
31
nvoB1Err_XXX
SNVT_switch
Boiler 2 Has Error
BI
32
DI
32
nvoB2Err_XXX
SNVT_switch
Boiler 3 Has Error
BI
33
DI
33
nvoB3Err_XXX
SNVT_switch
Boiler 4 Has Error
BI
34
DI
34
nvoB4Err_XXX
SNVT_switch
Boiler 5 Has Error
BI
35
DI
35
nvoB5Err_XXX
SNVT_switch
Boiler 6 Has Error
BI
36
DI
36
nvoB6Err_XXX
SNVT_switch
Boiler 7 Has Error
BI
37
DI
37
nvoB7Err_XXX
SNVT_switch
Boiler 8 Has Error
BI
38
DI
38
nvoB8Err_XXX
SNVT_switch
Boiler 1 Requires Service
BI
39
DI
39
nvoB1ReqSvc_XXX
SNVT_switch
Boiler 2 Requires Service
BI
40
DI
40
nvoB2ReqSvc_XXX
SNVT_switch
Boiler 3 Requires Service
BI
41
DI
41
nvoB3ReqSvc_XXX
SNVT_switch
Boiler 4 Requires Service
BI
42
DI
42
nvoB4ReqSvc_XXX
SNVT_switch
Boiler 5 Requires Service
BI
43
DI
43
nvoB5ReqSvc_XXX
SNVT_switch
Boiler 6 Requires Service
BI
44
DI
44
nvoB6ReqSvc_XXX
SNVT_switch
Boiler 7 Requires Service
BI
45
DI
45
nvoB7ReqSvc_XXX
SNVT_switch
Boiler 8 Requires Service
BI
46
DI
46
nvoB8ReqSvc_XXX
SNVT_switch
Boiler Address
AV
47
AO
47
nvi/nvoBlrAddr_XXX
SNVT_count_f
Power Level For The Boiler
AI
48
AI
48
nvoBlrPwrLvl_XXX
SNVT_lev_percent
Boiler Supply SP
AI
49
AI
49
nvoBlrSupSP_XXX
SNVT_temp_p
Heat Demand Type
AI
50
AI
50
nvoHtDemTyp_XXX
SNVT_count_f
System Sensor Temp
AI
51
AI
51
nvoSysSenTmp_XXX
SNVT_temp_p
Dhw Temp
AI
52
AI
52
nvoDhwTemp_XXX
SNVT_temp_p