Riello ProtoNode Start-up Guide
Page 10 of 43
3.4 Selecting the Desired Field Protocol and Enabling Auto-Discovery
3.4.1 Selecting Desired Field Protocol
ProtoNode FPC-N38
units use the “S” bank of DIP switches (S0 – S2) to select the Field
Protocol.
o
See the table in
for the switch settings for the ProtoNode.
o
The OFF position is when the DIP switches are set closest to the outside of the box.
ProtoNode FPC-N39
units do not use the “S” bank DIP switches (S0 – S2) to select a Field
Protocol.
o
On ProtoNode FPC-N39 units, these switches are disabled; the Field Protocol is always
LonWorks.
NOTE:
When setting DIP Switches, ensure that power to the board is OFF.
ProtoNode FPC-N38
S Bank DIP Switches
Profile
S0
S1
S2
BACnet/IP
Off
Off
Off
BACnet MS/TP
On
Off
Off
Metasys N2
Off
On
Off
Modbus TCP/IP
On
On
Off
BACnet MS/TP (single node)
Off
Off
On
S0
– S3 DIP
Switches
S Bank DIP Switch Location
Profile Settings for ProtoNode
Figure 5: S Bank DIP Switches
S0
S1
S2
S3
Off
On