-44-
No.PF
※※
-OMU0007-B
■
[F 5] FUNC terminal function setting
Analogue output, external input or copy function can be selected.
: Do not connect the grey wire when changing the setting.
•When the analogue output is selected
When the product with analogue voltage output is used, the output of 1 to 5 V or 0 to 10 V can be selected.
A flow value corresponding to 5 V (10 V) or 20 mA can be selected with the analogue output free range
function.
•When the external input is selected
The Accumulated Flow, Peak Value and Bottom Value can be reset remotely by an external input signal.
•Accumulated flow external reset: A function to reset the accumulated flow value when an external input
signal is applied.
In accumulated increment mode, the accumulated flow value will reset
to zero, and then increase from zero.
In accumulated decrement mode, the accumulated flow value will reset
to a set value, and then decrease from the set value.
: When the Accumulated Value has been stored to memory, every time the Accumulated Value External Reset is activated, the
memory will be accessed. Take into consideration the maximum number of times the memory can be accessed is1.5 million
times.
When using the product, it should be considered that the total number of external input resets and accumulated values stored
must not exceed 1.5 million cycles.
•Peak/Bottom value reset: A function to clear the peak value or bottom value in response to an external
input signal.
•When the copy function is selected
The set value of the monitor master side can be copied.