-84-
No.PF
※※
-OMZ0002
●
Product individual parameters (continued)
Index
Sub
index
Access
∗
1
Parameter
Data
type
∗
2
Initial
value
Data
storage
∗
3
Set value
∗
4
Remarks
dec
hex
1300
∗
5
0x0514
1
R/W
O
U
T
1 ac
c
u
m
ul
a
te
d f
lo
w
s
e
tti
n
g
AC1_L
(Mantissa L)
U16
0
Y
Setting range
0 to 9999
Setting of OUT1 mantissa
Unit: when “L” is selected
2
R/W
AC1_L
(Index L)
U16
0
Y
Setting range
0 to 6
Setting of OUT1 index
Unit: when “L” is selected
1310
∗
5
0x051E
1
R/W
AC1_L
(Mantissa Ft
3
)
U16
0
Y
Setting range
0 to 9999
Setting of OUT1 mantissa
Unit: when “Ft” is selected
2
R/W
AC1_L
(Index Ft
3
)
U16
0
Y
Setting range
0 to 6
Setting of OUT1 index
Unit: when “Ft” is selected
1410 0x0582
1
R/W
OU
T
2
s
e
tti
n
g
oUt2
(Selection output mode)
U8
0
Y
0: HYS (Hysteresis)
1: Wind
(Window comparator)
2: AC
(Accumulated output)
3: PLS
(Accumulated pulse)
4: Err (Error output)
5: oFF (Output OFF)
Setting of OUT2 output mode
2
R/W
2ot
(Selection of output type)
U8
0
Y
0: 2_P (Normal output)
1: 2_n (Reverse output)
Setting of OUT2 output normal and
reserved output.
1420 0x058C
1
R/W
O
U
T
2 s
w
it
c
h
poi
n
t.
P_2 (n_2)
(Selection of output
set value)
S16 2000
Y
Setting range
-200 to 4200
Setting of OUT2 output set value
(Hysteresis)
2
R/W
H_2
(Setting of OUT2
hysteresis)
S16 200
Y
Setting range
0 to 4400
Setting of OUT2 hysteresis
(Hysteresis)
3
R/W
P2L (n2L)
(Lower limit of
window
comparator)
S16 1200
Y
Setting range
-200 to 4200
Setting of OUT2 output set value
(Lower limit of window comparator)
4
R/W
P2H (n2H)
(Upper limit of
window comparator)
S16 2400
Y
Setting range
-200 to 4200
Setting of OUT2 output set value
(Upper limit of window comparator)
5
R/W
WH2
(Window comparator
hysteresis)
S16 400
Y
Setting range
0 to 2200
Setting of OUT2 hysteresis
(Window comparator)
6
R/W
dtH2
(Delay time at ON)
S16
0
Y
Setting range
0 to 6000
Setting of OUT2 delay time at ON
10 ms increment
7
R/W
dtL2
(Delay time at OFF)
S16
0
Y
Setting of OUT2 delay time at OFF
10 ms increment
1500
∗
5
0x05DC
1
R/W
O
U
T
2 ac
c
u
m
ul
a
te
d f
lo
w
s
e
tti
n
g
AC2_L
(Mantissa L)
U16
0
Y
Setting range
0 to 9999
Setting of OUT2 mantissa
Unit: when “L” is selected
2
R/W
AC2_L
(Index L)
U16
0
Y
Setting range
0 to 6
Setting of OUT2 index
Unit: when “L” is selected
1510
∗
5
0x05E6
1
R/W
AC2_L
(Mantissa Ft
3
)
U16
0
Y
Setting range
0 to 9999
Setting of OUT2 mantissa
Unit: when “Ft” is selected
2
R/W
AC2_L
(Index Ft
3
)
U16
0
Y
Setting range
0 to 6
Setting of OUT2 index
Unit: when “Ft” is selected
1600 0x0640
0
R/W
AC
(Setting of the accumulated
flow output direction)
U8
0
Y
0: Add (Addition)
1: dEC1
(Subtraction OUT1)
2: dEC2
(Subtraction OUT2)
Setting of the accumulated flow
output direction
1030 0x0406
0
R/W
FiL
(Digital filter)
U8
3
Y
0
:
0.05 sec
1
:
0.1 sec
2
:
0.5 sec
3
:
1.0 sec
4
:
2.0 sec
5
:
5.0 sec
Setting of digital filter
Содержание PF2MC7 Series
Страница 1: ...No PF OMZ0002 PRODUCT NAME Digital Flow Switch compatible MODEL Series Product Number PF2MC7 ...
Страница 56: ... 55 No PF OMZ0002 Bottom value display Peak value display ...
Страница 98: ... 97 No PF OMZ0002 Pressure loss PF2MC7501 500 L min PF2MC7102 1000 L min PF2MC7202 2000 L min ...
Страница 101: ... 100 No PF OMZ0002 Lead wire with M8 connector ZS 40 A M12 M8 conversion lead wire ZS 40 M12M8 A ...