[F22] Analogue output setting
This function is available when the model includes the analogue output.
Change the analogue output set value and analogue free range.
∗
When using a model without analogue outputs, this setting is not available and [- - -] will be displayed.
<Operation>
Press the UP or DOWN button in function selection mode to display [F22].
Press the SET button.
Move on to the setting of analogue output.
Setting of analogue output (voltage output only)
Press the UP or DOWN button to select 1 to 5 V output or 0 to 10 V output.
∗
: Only 4 to 20 mA is available for current output. The display will be [4-20] and not settable.
Press the SET button to set.
Move on to analogue free range mode setting.
Analogue free range mode setting
Press the UP or DOWN button to select the analogue free range mode.
[OFF] is selected
[ON] is selected
Press the SET button to set. Press the SET button to set.
Input of set value
Press the UP or DOWN button to set the flow value that will
output 5 V (10 V) or 20 mA.
The entered flow value can be in the range: 10% of the maximum rated flow, to the
max. displayable range.
Press the SET button to set.
Return to function selection mode.
[F22] Setting of analogue output completed.
Содержание PF2MC7 Series
Страница 1: ...No PF OMZ0002 PRODUCT NAME Digital Flow Switch compatible MODEL Series Product Number PF2MC7 ...
Страница 56: ... 55 No PF OMZ0002 Bottom value display Peak value display ...
Страница 98: ... 97 No PF OMZ0002 Pressure loss PF2MC7501 500 L min PF2MC7102 1000 L min PF2MC7202 2000 L min ...
Страница 101: ... 100 No PF OMZ0002 Lead wire with M8 connector ZS 40 A M12 M8 conversion lead wire ZS 40 M12M8 A ...