background image

Can be changed

10

1000

At the time of shipment

1

5

0

1050

100

10 % of the rated

flow range

100 % of the rated

flow range

Max. value of the

display range

Flow [l/min]

1000 l/min type

Analogue output [V]

Can be changed

10

1000

At the time of shipment

10

0

1050

100

10 % of the rated

flow range

100 % of the rated

flow range

Max. value of the

display range

Flow [l/min]

1000 l/min type

Analogue output [V]

Error display function

When an error or abnormality arises, the location and contents are displayed.

Analogue output free range function

This function allows a fl ow that generates an output of 5 V (or 10 V 
when 0 to 10 V is selected) or 20 mA to be changed.
The value can be changed between 10 % of the maximum value of 
the rated fl ow and the maximum value of the display range.

For analogue voltage output of 0 to 10 V

Display

Error name

Description

Action

Applicable model

PFMC7

series

PFMC7-L

series

OUT1 over current 
error

A load current of 80 mA or more is 
applied to the switch output (OUT1).

Eliminate the cause of the over 
current by turning off the power 
supply and then turning it on again.

OUT2 over current 
error

A load current of 80 mA or more is 
applied to the switch output (OUT2).

Instantaneous fl ow 
error

The fl ow has exceeded the upper limit 
of the fl ow display range.

Decrease the fl ow rate.

Reverse fl ow error

There is a reverse fl ow equivalent to 
-5 % or more.

Change the fl ow to the correct 
direction.

(                         )

Alternately displays 

[999] and [999999]

Accumulated fl ow 
error

The accumulated fl ow has exceeded 
the accumulated fl ow range.

Reset the accumulated fl ow.

 (Flashing)

x 10

6

Accumulated fl ow 
error

The accumulated fl ow has exceeded 
the accumulated fl ow range.

Reset the accumulated fl ow.

System error

An internal data error has occurred.

Turn the power OFF and turn it ON 
again.

System error

An internal data error has occurred.

Turn the power OFF and turn it ON 
again.

Outside of zero-clear 
range

During zero-clear operation, the fl ow rate of 

±

5 % F.S. or more is applied. (The mode is 

returned to measurement mode after 1 second.)

Retry the zero-clear operation without 
applying fl uid.

Version does not 
match

The IO-Link version does not match that 
of the master.

Ensure that the master IO-Link 
version matches the device version.

If the error cannot be solved after the instructions above are performed, please contact SMC for investigation.

25

PFMC7(-L) 

Series

Содержание PF2A Series

Страница 1: ...product Flow ratio 2 Smallest settable increment 10 1000 1000 L type 5 500 500 L type 5 l min for t PF2A serie l PFG300 Series RoHS min the for the existing es model l Digital Flow Monitor Allows for...

Страница 2: ...nding on application The accumulated indication shows the operating flow rate or residual amount of N2 etc in a gas cylinder Flow control of equipment main line and branch line Applications Remote con...

Страница 3: ...sub screen is set to mode display ModE LoC is displayed when the data storage lock is enabled Except for when the version does not match or when in SIO mode Display function Displays the output commun...

Страница 4: ...Visualization of settings Allows for the monitoring of remote lines Easy screen switching Simple 3 step setting Pressing the and buttons simultaneously for a minimum of 1 second will make the set valu...

Страница 5: ...e output free range function Error display function Copy function Selection of power saving mode Functions pp 26 to 28 Output operation Simple setting mode Display colour Delay time setting Digital fi...

Страница 6: ...flow type 1 l min PF2M7 L PFG300 PFG300 PF2A PF3A7 H L PFMB PFMC7 L 1 10 1 10 1000 1 20 2000 2 5 500 5 10 1000 1 20 2000 2 5 500 5 2 200 2 1 100 1 0 5 50 5 3 3 2 0 3 0 3 0 1 0 1 0 05 5 0 1 0 0 05 5 5...

Страница 7: ...Hysteresis mode Variable Window comparator mode Variable Hysteresis mode Variable Window comparator mode Variable Hysteresis mode Variable Window comparator mode Variable Hysteresis mode Variable Win...

Страница 8: ...7...

Страница 9: ...L Series How to Order p 11 Specifications p 12 Flow Range p 13 Analogue Output p 13 Pressure Loss p 13 IN Side Straight Piping Length and Accuracy p 13 Internal Circuits and Wiring Examples p 14 Cons...

Страница 10: ...equired order with the part numbers listed below Part no Option Note ZS 40 A Lead wire with M8 connector Length 3 m ZS 42 A Bracket Mounting screw for PFMC7501 7102 M3 x 5 2 pcs ZS 42 B Bracket Mounti...

Страница 11: ...screen White Main screen 4 digits 7 segments Sub screen 6 digits 11 segments Indicator LED LED ON when switch output is ON OUT1 OUT2 Orange Environmental resistance Enclosure IP65 Withstand voltage 2...

Страница 12: ...erseas use only The SI unit type is provided for use in Japan in accordance with the New Measurement Act 7 Fixed units Instantaneous flow l min Accumulated flow L Calibration certificate None A 9 Yes...

Страница 13: ...2 The time from when the flow is changed by a step input when the flow rate changes from 0 to the maximum value of the rated flow range instantaneously until the analogue output reaches 90 of the rate...

Страница 14: ...A current flows it is possible that the accuracy is not satisfied below 0 5 V The minimum value of the rated flow range will change according to the setting of the zero cut function 0 l min A 2 B Volt...

Страница 15: ...Analogue 1 to 5 V output type PFMC7 C NPN 1 output Analogue 4 to 20 mA output type PFMC7 D Max applied voltage 28 V Max load current 80 mA Internal voltage drop 1 V or less C Analogue output 1 to 5 V...

Страница 16: ...1 5 V or less L3 Analogue output 1 to 5 V or 0 to 10 V Output impedance 1 k L4 Analogue output 4 to 20 mA Max load impedance 600 Min load impedance 50 Max applied voltage 30 V Max load current 80 mA I...

Страница 17: ...3 Flow rectifier Stainless steel 304 4 Sensor chip Silicon 5 Printed circuit board GE4F 6 Gasket HNBR 7 Body Aluminum alloy Anodized 8 Mesh Stainless steel 304 9 Spacer PPS 10 O ring HNBR 11 Holder St...

Страница 18: ...Material Heat and oil resistant PVC Finished outside diameter 4 Symbol Model Port size A B D E F H K L N PFMC7501 7102 L Rc1 2 NPT1 2 70 30 60 6 41 2 15 14 26 18 13 6 PFMC7202 L Rc3 4 NPT3 4 G3 4 90 3...

Страница 19: ...outputs NPN PNP switching type Analogue voltage output 1 2 SV 2 outputs NPN PNP switching type Analogue current output 2 XY 2 outputs NPN PNP switching type Copy function 1 Can switch between 1 to 5 V...

Страница 20: ...w Unit 7 Instantaneous flow l min cfm ft3 min Accumulated flow L ft3 L x 106 ft3 x 106 Display range Instantaneous flow 25 to 525 l min 50 to 1050 l min 100 to 2100 l min Accumulated flow 9 0 to 999 9...

Страница 21: ...Sensor Main circuit Main circuit Main circuit Load Load Load Load Load Load Load Load Load Load Load Load Load Load Max 28 V 80 mA Black OUT1 White OUT2 Blue DC Load Load Max 80 mA Brown DC Black OUT...

Страница 22: ...llows for mounting in four orientations Bracket configuration allows for mounting in four orientations 1 6 7 2 7 2 5 2 5 2 5 2 30 30 25 1 5 2 7 7 7 20 20 Sensor connector 4 x 2 6 Depth 7 or less Power...

Страница 23: ...Panel mount adapter Front protection cover Part no ZS 46 D Power supply output connection lead wire Part no ZS 46 5L Sensor connector Part no ZS 28 CA 4 1 1 to 5 V or 4 to 20 mA Pin no Terminal 1 DC...

Страница 24: ...s 24 or more 31 0 0 4 24 or more 31 x n pcs 3 5 x n pcs 1 4 x R 2 o r m o r e 31 0 0 4 Dimensions Multiple 2 pcs or more secure mounting Horizontal Panel mount example Horizontal Panel mount example...

Страница 25: ...external inputs and the accumulated value memorizing time interval should not exceed 1 million times Peak Bottom value reset Peak and bottom value are reset Forced output function The output is turned...

Страница 26: ...ing it on again OUT2 over current error A load current of 80 mA or more is applied to the switch output OUT2 Instantaneous flow error The flow has exceeded the upper limit of the flow display range De...

Страница 27: ...when OFF 1 V or 0 V when 0 to 10 V is selected or 4 mA Also an increase or decrease of the flow will not change the on off status of the output while the forced output function is activated Accumulat...

Страница 28: ...pply and then turning it on again Instantaneous flow error The flow rate exceeds the maximum value of the display range Decrease the flow rate Reverse flow error There is a reverse flow equivalent to...

Страница 29: ...o the slave monitors reducing setting labor and minimizing the risk of setting mistakes The set value can be copied to up to 10 flow monitors simultaneously Maximum transmission distance 4 m Selection...

Страница 30: ...of SMC products with production equipment for the manufacture of weapons of mass destruction WMD or any other weapon is strictly prohibited 2 The exports of SMC products or technology from one countr...

Страница 31: ...alia it Latvia 371 67817700 www smc lv info smc lv Lithuania 370 5 2308118 www smclt lt info smclt lt Netherlands 31 0 205318888 www smc nl info smc nl Norway 47 67129020 www smc norge no post smc nor...

Отзывы: